Toshiba 4200FA Manual De Usuario

Descargar
Página de 66
TOSHIBA 
 
44 
5.15.4  Line-4 System Messages 
Line-4 messages reflect the UPS operating conditions. Warning messages will be 
displayed when an abnormal operating condition occurs. The following chart shows 
the allowable Line-4 messages. 
Line-4 Messages 
Displayed Message 
Translation 
PHEI 
Displayed when Input Phase rotation has been wired 
in a counter-clockwise rotation. 
I/O NOT SYNCHRONIZE 
Displayed when input and output frequencies are not 
synchronized.  (Abnormal) 
* AUTOTRANSFER * 
Displayed when Auto-transfer to Bypass is active (i.e. 
current limit reached).  (Abnormal) 
* LOW BATTERY * 
Displayed when battery voltage is low (abnormal) or 
the UPS batteries have failed self-diagnostic test.  
(Abnormal) 
* UPS OL: REDUCE LOAD * 
Displayed when UPS has tripped due to an overload 
condition.  (Abnormal) 
* DCOC * 
Displayed when the UPS has an internal failure. 
(Abnormal) 
* DCOV * 
Displayed when the UPS has an internal DC bus 
over-voltage. (Abnormal) 
* DCUB * 
Displayed when the UPS has an internal DC bus 
unbalance referenced to Neutral. (Abnormal) 
* OL * 
Displayed when UPS has tripped due to an overload 
condition.  (Abnormal) 
* FUSE * 
Displayed when an internal transistor fuse opens. 
* INOV * 
Displayed when inverter output over-voltage has 
occurred. (Abnormal) 
* INUV * 
Displayed when inverter output under-voltage has 
occurred. (Abnormal) 
* BATT. OH *OR MCCB-B OPEN 
Displayed when the optional battery over-temp 
sensor has activated, or if the external battery 
disconnect is open. (Verify TB3-5, 6) 
* MM/DD/YY (DAY)   HH:MM * 
Displayed when none of the above abnormal 
conditions are present. (Normal) 
* TRANSFER INHIBITED * 
Displayed when key switch position is changed and 
frequency is not synchronized. (Abnormal) 
* ENTER FOR DETAILS * 
Displayed when a Fault or Faults have occurred. 
(Abnormal) 
 Note: 
1) 
Line-4 will be blank when the BATT key is pressed during Battery Backup Mode with 
normal battery voltage. 
 
2) 
The # symbol signifies numerical values or other information supplied by the UPS.