5.22.6  Output Voltage Adjustment 
When the MENU key is pressed and held 3-4 seconds during normal 'AC Input Mode' 
of operation, the LCD screen displays the output voltage on the present output 
voltage adjust screen: 
 
  OUTPUT VOLT.  ADJUST 
OUTPUT VOLTAGE.=###% 
>F1:DATA  SET  MODE 
∆/∇ :PREV/NEXT  SCREEN 
 
 
Press the F1 key to display the following active adjustment screen: 
 
 
    OUTPUT VOLT. ADJUST 
REFERENCE ADJUST: ## 
∆/∇ :CHANGE  DATA 
>ENTER: ACCEPT  CHANGE 
 
 
The locations marked ## will show the numerical value of the allowable voltage 
adjustment parameter values. Press the 'up' and 'down' arrow keys to adjust the 
setting from between 
±5 volts. This will cause the unit's output voltage to adjust to 
within 
±2% of its nominal value. 
 
If the inverter is not running, and the output voltage cannot be adjusted; the following 
message will be displayed: 
 
OUTPUT VOLT. ADJUST 
ADJUST PROHIBITED 
DATA CANNOT CHANGE 
>
∆/∇:PRV/NEXT SCREEN 
 
 
Pressing the F1 key will have no effect on this display screen 
 
 
5.22.7  Charge Mode Select 
Press the MENU key to access the menu data screens and press the 'down' arrow 
key to scroll to the “Charge Mode Select” adjustment screen display: 
 
  CHARGE  MODE  SELECT 
EQUAL  CHARGE>OFF  ON 
>F1:DATA  SET  MODE 
>
∆/∇:PRV/NEXT SCREEN 
 
Press the F1 key to display the following active adjustment screen: 
 
CHARGE  MODE  SELECT 
EQUAL  CHARGE>OFF  ON 
>
∆/∇:CHANGE  DATA 
>ENTER:ACCEPT  CHANGE 
 
Note: Please consult with the factory when using this option. DAMAGE to the 
battery system will occur if this is used improperly.