Toshiba 4200FA Manual De Usuario

Descargar
Página de 66
TOSHIBA 
 
56 
5.22.8  Reset to Default Settings 
Press the MENU key to access the menu data screens and press the 'down' arrow 
key to scroll to the original factory 'default settings' adjustment screen display: 
 
       MENU DATA RESET 
DATA  INITIALIZATION 
>F1:  TO  ACCESS  RESET 
>
∆/∇:PRV/NEXT SCREEN 
 
Press the F1 key to display the following active adjustment screen: 
 
 
        MENU DATA RESET 
DATA  INITIALIZATION 
> MENU:  NO  DATA  RESET 
>ENTER: ACCEPT CHANGE 
 
When the ENTER key is pressed the following factory defaults are reset: 
1)  Resets the voltage-reference setting to +0 
2)  Resets the buzzer volume to 'loud' 
3)  Resets the serial station address to 31h 
4)  Resets the idle mode to 3 minutes 
 
Press the MENU key to abandon the operation and return to the menu data screen. 
 
5.23 Overload 
Operation 
When the UPS is operating and an overload condition is first detected, the following “Overload 
Warning” screen is displayed. 
 
-  UPS ON-LINE  - 
OUTPUT VOLTAGE= ###V 
OUTPUT CURRENT= ###% 
*  UPS OL: REDUCE LOAD * 
 
After a period of time, if the overload is still not reduced and the STOP/RUN key switch is in the 
RUN position, the UPS will automatically transfer to Bypass. If the overload condition is still 
present, the following screen will be displayed: 
 
-  BYPASS OPERATION  - 
OUTPUT VOLTAGE=208 
CURRENT= 114/116/114% 
*  UPS OL: REDUCE LOAD * 
 
If the STOP/RUN key switch is in the STOP position; the UPS is in the Bypass Mode and, if the 
overload condition is still present, the following screen will be displayed: 
 
-  BYPASS OPERATION  - 
OUTPUT VOLTAGE=208 
CURRENT= 114/116/114% 
*  UPS OL: REDUCE LOAD *