Toshiba lf516 Manual De Usuario

Descargar
Página de 157
 
 
 107 − 
 
6 F 8 A 0 9 3 4  
10.1 Digital I/O Specifications 
The specifications of the digital I/O terminals for the converter for electromagnetic flowmeter: LF546 are 
as follows: 
„  Digital Output 1(DO1 )     
Output type:     
Transistor open collector 
Number of outputs: 
Capacity:         
30 V dc, 200 mA maximum 
 
„  Digital Output 2(DO2 ) 
Output type:     
Solidstate relay (non polarity) 
Number of outputs: 
Capacity:         
150 V dc, 150 mA maximum 
 
150 V ac(peal-to-peak), 100 mA maximum 
„  Digital Input (DI ) 
Input signal:     
20 to 30 V dc voltage signal 
• 
High input level—20 to 30 V dc 
• 
Low input level—2 V dc maximum 
Input resistance:   
Approximately 2.7 kΩ 
Number of inputs:   
One point 
 
• 
Each I/O terminal can be used as a specified function terminal when selected. 
• 
Terminal COM is the signal COMMON for the other three terminals (DO1, DO2 and DI). 
• 
Each terminal is isolated from the internal circuits.  
(The output terminals are not isolated from each other.) 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Flowmeter 
 
Solidstate relay 
 
Transistor open collector 
(Standard) 
 
Voltage input (DI) 
 
Contact output 2 (DO2) 
Contact output 1 (DO1) 
Resistor 
Photo coupler 
 
 
COM 
DI 
DO2 
DO1