4.4 Grounding 
 
 
CAUTION
 
„  Do not wire cables and replace parts 
when power is supplied. 
„  Do not work on piping and wiring with wet hands
 
DON’T
 
Wiring work and replacing 
parts in the power-on state 
may cause electric shock. 
 
DON’T
 
Wet hands may result in electric shock
 
 
Ground as shown in Figure 4.10. Make the grounding wire as short as possible. Use 
grounding wire material of IV wire 5.5mm
or more. Do not share a grounding wire 
with other instruments where grounding current may flow. (An independent 
grounding is preferable.)
 
 
 
 
 
 
     
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Figure 4.10    Grounding the LF516/LF546 Type 
 
 
Grounding terminal
grounding resistance 
100Ω or more 
• If the piping material is conductive, connect 
the grounding wires to the both ends of the 
piping flange. 
• If the piping material is non-conductive, perform 
grounding (grounding resistance 100Ω or less). 
Conductive material pipe 
Example: Metal, etc. 
Piping of non-conductive material 
Example: Resin or metal piping whose 
inside is resin-lined, etc. 
 