4. Equipment Specifications 
 
Item Specification 
Operating Environment 
Indoors, less than 1000m above sea level, do not 
expose to direct sunlight or corrosive / explosive gasses 
Operating Temperature 
-10 
 +40
°
C (+14 
 +104
°
F) 
Storage Temperature 
-25
°
 +65
°
C (-13 
 +149
°
F) 
Relative Humidity 
20% 
 90% (without condensation) 
Vibration 
5.9m/s
2
 {0.6G} or less (10 
 55Hz) 
Grounding 
SHIELD terminal connected to isolated network ground 
via 200
Ω
 resistance. 
Cooling Method 
Self-cooled 
 
 
 
5.  Maintenance And Inspection 
Preventive maintenance and inspection is required to maintain the MDB-100 Modbus 
interface in its optimal condition and to ensure a long operational lifetime.  Depending 
on usage and operating conditions, perform a periodic inspection once every three to 
six months.  Before starting inspections, always turn off all power supplies to 
connected drives, and wait at least five minutes after each drive’s “CHARGE” lamp 
has gone out. 
 
DANGER!
 
 Do not touch any internal parts with power applied 
to the drives, or for at least 5 minutes after power to the drives has been 
removed.  A hazard exists temporarily for electrical shock even if the source 
power has been removed.
 
 
Inspection Points 
• 
Check that the Modbus network connector screws and terminal block plug are not 
loose.  Tighten if necessary. 
• 
Check that the drive communication cables are not loose.  Reinsert if necessary. 
• 
Visually check all wiring and cables for damage.  Replace as necessary. 
• 
Clean off any accumulated dust and dirt. 
• 
If use of the MDB-100 is discontinued for extended periods of time, apply power 
at least once every two years and confirm that the unit still functions properly. 
• 
Do not perform hi-pot tests on the drives or MDB-100 interface, as they may 
damage the units. 
 
Please pay close attention to all periodic inspection points and maintain a good 
operating environment.