7.  Network Characteristics Configuration 
The MDB-100 interface board uses an 8-position DIP switch (labeled SW1) to 
configure the Modbus network communication characteristics.  The switch settings 
are only read during initialization, so if a change is made to any of the switches on 
SW1, the MDB-100 must be reset in order to enable the new settings.  The various 
configuration settings of switch SW1 are as follows: 
 
Communication Method: 
SW1 # 
Function 
OFF 
Modbus RTU (factory default) 
ON Modbus 
ASCII 
 
Baud Rate: 
SW1 # 
4 3 2 
Function 
OFF OFF OFF 300 
baud 
OFF OFF  ON 600 
baud 
OFF ON OFF 
1200 
baud 
OFF ON  ON 2400 
baud 
ON OFF OFF 
4800 
baud 
ON 
OFF 
ON 
9600 baud (factory default) 
ON ON OFF 
19.2 
kbaud 
ON ON ON 
38.4 
kbaud 
 
Parity: 
SW1 # 
6 5 
Function 
OFF 
OFF  even parity (factory default) 
OFF ON odd 
parity 
ON 
OFF  no parity (2 stop bits) 
ON 
ON 
no parity (1 stop bit) - applies only to RTU mode 
 
Protocol: 
SW1 # 
Function 
OFF 
Modicon Modbus (factory default) 
ON 
DO NOT SELECT (reserved for future expansion) 
 
Station Number Origin: (refer to section 8) 
SW1 # 
Function 
OFF 
Drive A’s inverter number parameter (factory default) 
ON 
Switch SW2 address setting