placed on the UPS increases the fan speed will increase.  The 
temperature of the environment the UPS is operating in can also 
cause the fan speed to increase.  (For a more detailed explanation of 
the variable speed fan function refer to appendix B) 
 
Battery Check Function 
During startup the UPS will perform an automatic 'Battery Check' to 
detect whether a problem exists in the battery circuit.  If the batteries 
pass the test, the unit will start normal operation.  If a problem is 
detected during the test the “Warning/Fault” LED will activate.  Other 
LED’s may also activate.  If this occurs please refer to the 
“Troubleshooting” section on page 20 for a description of the 
problem and possible solutions.  It is important to note that when 
the UPS has detected bad batteries, the battery backup mode is 
disabled.
  The unit will continue to operate and provide clean power; 
however, since there is no battery power available, the unit cannot 
provide backup power if input power is lost. 
 
The Function Control Button 
The function control button is located on the display panel (see 
“Display Panel Layout”, page 11).  This button is used to perform 
several different UPS operations, including initiating self test, 
providing programming options, and silencing the alarm.  A brief 
description of each function follows along with a step by step guide 
to accessing each function. 
 
1)  Self-Test.  In order to perform a self-test the UPS must be 
operating in the normal mode (see “UPS Display Status and 
Operating Condition”, page 13).  To initiate the self-test simply 
press and hold the Function Control button until all the LED’s 
activate.  The self-test also performs the same battery check 
described above. 
 
2)  Alarm Silence.  The alarm silence feature is used to stop the 
audible alarm from sounding.  Any time the audible alarm is 
sounding pressing the Function Control button will silence the 
alarm. 
 
3)  Programming Mode.  There are three programming options: 
load shed, output enable/disable after input overvoltage backup, 
and reset battery installed date.  In order to enter the 
programming mode the UPS must first be operating in Bypass 
mode without faults (see “Stopping the UPS: Option 1”, page 
12).  Then press and hold the Function Control button.  (“Press 
and hold” always means to hold until the unit gives audible 
feedback).  The unit will give an audible feedback indicating the 
unit is in programming mode.  (If at anytime while the UPS is in 
the programming mode there is one minute of inactivity the UPS