CONTROL BOARD SETTINGS
THESE SETTINGS SHOULD BE ADJUSTED ONLY BY AN EXPERIENCED INSTALLER OR TECHNICIAN!
LEARN/RESET:
1)
 
Use to set transmitter code in control board memory.
2) Press this button to clear the diagnostic and error LEDs.
DIP switches
(To change these settings, you must turn power
OFF; move the switch; then turn power back ON.
)
SWNG/SLD (swing or slide gate operation): SWNG = swing gate  SLD = slide gate  [factory default is SLD].
MAST/SLV (master or slave unit): This DIP switch must be set to MAST for single gate applications.  For dual gate
applications set one control board to MAST and the other to SLD [factory default is MAST].  See installing a Dual
System on pages 22-23.
GATE R/L (gate opens right or left)The direction a gate opens is determined by standing inside the property and
facing toward the gate.  Set the DIP switch to R for a gate that opens to the right.  Set the DIP switch to L for a gate
that opens to the left.
SEQUENCE 1: This DIP switch is used for sequencing slide gates [factory default is OFF]. For single gate
applications this switch MUST be set to OFF.
SEQUENCE 2:
 Same as SEQUENCE 1 above.
TMR. OFF/ON: (auto-close timer OFF or ON; close timer is set to 1 second at the factory): When this DIP switch
is set to ON, the CLOSE TIMER potentiometer must be adjusted [factory default is OFF].
NORM/LEARN (normal control board mode or learn mode): Function not available on this control board (function
will be activated on future boards).
OPEN/CLOSE: In the event of a low voltage lockout the operator will go to either the OPEN or CLOSE position and
shut down. Set this DIP switch for for desired position.
PWR OK
TIMER ON
OBSTRUCT
LEARN/RESET
GTO Inc., Tallahassee, FL
12345678
ON
SWNG/SLD
MAST/SLV
GATE R/L
SEQUENC 1
SEQUENCE 2
TMR. OFF/ON
NORM/LEARN
OPEN/CLOSE
Potentiometers 
(All potentiometers are set to MIN at the factory.  The size and type of gate installation must be
accommodated by adjusting the potentiometers.  HOWEVER–potentiometer settings should not be used to compensate
for worn, damaged, or incorrect gate hardware.)
CLS. SENS. (closing sensitivity): Adjusts obstruction sensitivity of the gate
in closing mode.  The MIN setting is for minimum gate force.  The MAX
setting is for maximum gate force (i.e., the operator will require greater
resistance before obstructing).
OPN. SENS. (opening sensitivity): Adjusts obstruction sensitivity of the  gate
in opening mode (see CLS. SENS. above).
INERTIA:  Fine tunes the operator obstruction settings in the open and close
modes.  This potentiometer can be adjusted to allow the operator to push
against an obstruction for a maximum of 2 seconds before obstructing (i.e.,
stopping and reversing).
CLOSE TIMER (Controls the auto-close feature [factory default is 1 second]):
disabled and enabled with the TMR. OFF/ON DIP switch (see DIP switches
above).  The potentiometer adjusts the amount of time the gate will remain
open before it closes.  The limits are 1 to 120 seconds.
MIN
MAX
INERTIA
MIN
MAX
CLS. SENS.
MIN
MAX
OPN. SENS.
1
120
TIMER