RANGE: Thermostat 
(Part No. 618-225-02) 
60
° F ( ± 2° ) to 90° F( ± 4° )  
SENSING   
BULB LOCATION  
THERMOSTAT 
A  cross  ambient  thermostat  is  used  to  maintain  the 
desired  comfort  level.  The  thermostat  reacts  only  to  a 
change in temperature at the bulb location. Important to 
the successful operation of the unit is the position of the 
sensing bulb in relation  to the evaporator.  
TESTING THE THERMOSTAT
Remove  the  wires  from  the  thermostat.  Turn  the 
thermostat to its coldest position. Check to see if there is 
continuity between the two terminals. Turn the thermostat 
to  its  warmest  position.  Check  continuity  to  see  if  the 
thermostat contacts open.
Note: The temperature must be within the range listed to 
check the thermostat. Refer to the troubleshooting section 
in  this  manual  for  additional  information  on  thermostat 
testing. 
The HazardGard unit is designed to operate at low outside 
ambient temperatures. This is accomplished by the use 
of  a  bypass  valve  installed  in  the  refrigeration  circuit. 
The  valve  is  connected  between  the  discharge  line  at 
the compressor and the suction process tube. The valve 
responds to suction pressure which, when reduced in the 
system,  causes  the  valve  to  open  and  bypass  hot  gas 
from the high pressure side to the low pressure side of 
the system. The hot gas entering the compressor mixes 
with the cool gas returned through the suction line, thus 
increasing  the  suction  pressure. The  valve  is  preset  to 
open  when  the  suction  pressure  reaches  50  psig. This 
pressure setting cannot be altered. The system can be 
operated at outdoor temperatures as low as 45
°F before 
the evaporator coil will begin to accumulate frost. 
To determine if the valve operates, block the return air to 
the  evaporator coil. Turn on the unit and touch the tube 
at the  bypass valve outlet which connects to the suction 
process  tube.  When  the  low  side  pressure  reaches 
approximately 50 psig, the valve will begin to open and 
the  tube  will  get  hot.  This  method  will  determine  if  the 
valve is responding to the suction pressure change.
LOW AMBIENT BYPASS VALVE
ELECTRIC SHOCK HAZARD 
WARNING
Disconnect  power  to  the  unit  before 
servicing.  Failure  to  follow  this  warning 
could result in serious injury or death. 
Sealed  Refrigeration  System  contains 
refrigerant and oil under high pressure.
Proper safety procedures must be followed, 
and  proper  protective  clothing  must  be 
worn when working with refrigerants.
Failure to follow these procedures could 
result in serious injury or death. 
WARNING
HIGH PRESSURE HAZARD 
LOW AMBIENT   
BYPASS VALVE  