Cisco Nexus 7000 System Site Preparation Guide
OL-15846-01
A P P E N D I X
B
Cabinet and Rack Requirements
This appendix describes the cabinet and rack requirements and includes these sections:
  •
General Requirements for Cabinets and Racks
This section provides the Nexus 7000 Series requirements for the following types of racks and cabinets, 
assuming an external ambient air temperature range of 41 to 104°F (5 to 40°C):
  •
Standard perforated cabinets
  •
Solid-walled cabinets with a roof fan tray (bottom to top cooling)
  •
Standard open racks
  •
Four-post telco racks
Note
If you select an enclosed cabinet, we recommend that you use one of the following thermally validated 
types: standard perforated or solid-walled with a fan tray.
To correctly install the Nexus 7000 Series in a hot-aisle cold-aisle environment, you should fit a cabinet 
with baffles to prevent exhaust air from recirculating.
Note
The verified cabinet vendors for the Nexus 7000 Series are Panduit and Chatsworth.
The rack or cabinet used to hold a Nexus 7000 Series should meet the following requirements:
  •
Use a standard 19-inch, four-post Electronic Industries Alliance (EIA) cabinet or rack, with 
mounting rails that conform to English universal hole spacing per section 1 of the 
ANSI/EIA-310-D-1992 standard.
  •
Have at least 21 rack units (RU) of usable vertical rack space for one Nexus 7000 series device and 
42 RU for two Nexus 7000 Series devices (45 RU is recommended).
Each of the following optional requirements are site specific:
  •
Accommodate up to two Nexus 7000 10-slot chassis and provide cable management for up to 384 
ports for each Nexus 7000 series device.
  •
Provide the features required for the AC power distribution units (PDUs) for the power supplies 
installed in each chassis.