Puls UB10.241 UPS Guia De Especificaciones
UB10.241
U–Series
24V, 10A, DC-UPS
17. EMC
The unit is suitable for applications in industrial environment as well as in residential, commercial and light industry
environment without any restrictions. CE mark is in conformance with EMC guideline 89/336/EEC and 93/68/EEC and
the low-voltage directive (LVD) 73/23/EEC, 93/68/EEC.
environment without any restrictions. CE mark is in conformance with EMC guideline 89/336/EEC and 93/68/EEC and
the low-voltage directive (LVD) 73/23/EEC, 93/68/EEC.
A detailed EMC Report is available on request.
EMC Immunity
EN 61000-6-1, EN 61000-6-2
Generic standards
Electrostatic discharge
EN 61000-4-2
Contact discharge
Air discharge
Air discharge
8kV
15kV
15kV
Criterion A*)
Criterion A *)
Criterion A *)
Electromagnetic RF field
EN 61000-4-3 80MHz-1GHz
10V/m
Criterion
A
Fast transients (Burst)
EN 61000-4-4
Out- and input lines
2kV
Criterion A
Signal lines **)
2kV
Criterion A
Surge voltage
EN 61000-4-5
Output + Æ -
Input + Æ -
+ / - Æ housing
Input + Æ -
+ / - Æ housing
500V
500V
500V
500V
500V
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
15/23
Conducted disturbance
EN 61000-4-6
0,15-80MHz
10V
Criterion A
*) DIN-Rail
earthed
**) Tested with coupling clamp
EMC Emission
EN 61000-6-3, EN 61000-6-4
Generic standards
Conducted emission
EN 55022
Input lines
Class B *)
EN 55022
Output lines
Class B *)
Radiated emission
EN 55011, EN 55022
Class B
This device complies with FCC Part 15 rules.
Operation is subjected to the following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
*)
Informative measurement with voltage probe
Switching frequencies
The DC-UPS has three converters with three different
switching frequencies included.
switching frequencies included.
Switching frequency of boost converter
100kHz
Constant frequency
Switching frequency of electronic output current limitation
78kHz
Constant frequency
Switching frequency of battery charger
19.5kHz
Constant frequency
June. 2010 / Rev. 1.3 DS-UB10.241-EN
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current.
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current.