Puls UB10.241 UPS Guia De Especificação

Página de 23
 
 
 
UB10.241 
 
  USeries 
24V, 10A, DC-UPS 
 
 
 
17.  EMC 
 
The unit is suitable for applications in industrial environment as well as in residential, commercial and light industry 
environment without any restrictions. CE mark is in conformance with EMC guideline 89/336/EEC and 93/68/EEC and 
the low-voltage directive (LVD) 73/23/EEC, 93/68/EEC. 
A detailed EMC Report is available on request. 
 
EMC Immunity 
EN 61000-6-1, EN 61000-6-2 
 
Generic standards 
Electrostatic discharge  
EN 61000-4-2 
Contact discharge 
Air discharge 
8kV 
15kV 
Criterion A*) 
Criterion A *) 
 
  Electromagnetic RF field 
EN 61000-4-3 80MHz-1GHz 
10V/m 
Criterion 
  Fast transients (Burst) 
EN 61000-4-4 
Out- and input lines 
2kV 
Criterion A 
   
 
Signal lines **) 
2kV 
Criterion A 
Surge voltage 
EN 61000-4-5 
Output + Æ - 
Input + Æ - 
+ / - Æ housing 
500V 
500V 
500V 
Criterion A 
Criterion A 
Criterion A 
 
15/23 
  Conducted disturbance 
EN 61000-4-6 
0,15-80MHz 
10V 
Criterion A 
*) DIN-Rail 
earthed 
 
**)  Tested with coupling clamp 
 
EMC Emission 
 
EN 61000-6-3, EN 61000-6-4 
 
Generic standards 
  Conducted emission  
EN 55022 
Input lines 
Class B *) 
   
EN 55022 
Output lines 
Class B *) 
  Radiated emission 
EN 55011, EN 55022 
 
Class B 
This device complies with FCC Part 15 rules.  
  Operation is subjected to the following two conditions: (1) this device may not cause harmful interference, and (2) this 
device must accept any interference received, including interference that may cause undesired operation. 
*) 
Informative measurement with voltage probe 
 
 
Switching frequencies 
The DC-UPS has three converters with three different 
switching frequencies included. 
 
  Switching frequency of boost converter 
100kHz 
Constant frequency 
  Switching frequency of electronic output current limitation 
78kHz  
Constant frequency 
  Switching frequency of battery charger 
19.5kHz 
Constant frequency 
 
June. 2010 / Rev. 1.3  DS-UB10.241-EN 
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time  
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current. 
www.pulspower.com   Phone +49 89 9278 0    Germany