Section 4 - Commissioning Process
21
Manager Gateway’s default IP address:
192.168.99.100.
192.168.99.100.
5. Energize the +24Vdc supply attached to the
Manager Gateway.
NOTE
Be sure the computer or network switch is
powered on before the Manager Gateway.
Failure to power up the Manager Gateway
before it is attached to an energized network
will result in failure of the Manager Gateway
Ethernet communications. The correct power
up sequence must be used.
powered on before the Manager Gateway.
Failure to power up the Manager Gateway
before it is attached to an energized network
will result in failure of the Manager Gateway
Ethernet communications. The correct power
up sequence must be used.
6. Verify you can successfully ping (command
executed at the Windows command prompt)
the Manager Gateway to validate Ethernet
communication.
the Manager Gateway to validate Ethernet
communication.
7. Launch the Embedded webpage on the
Manager Gateway (Admin Toolset) by typing
the following in the Internet Explorer menu
bar: http://192.168.99.100.
the following in the Internet Explorer menu
bar: http://192.168.99.100.
8. Click the Yes button if the Security Alert
window appears. Sign in using the default
user name: system and password: system.
9. Click Interfaces. Select either DHCP or Static
IP address type. Assign a valid IP Address,
Subnet Mask and Default Gateway for the
network the Manager Gateway will reside
Subnet Mask and Default Gateway for the
network the Manager Gateway will reside
on. Click Apply Changes.