Section 4 -  Commissioning Process 
 
21 
Manager  Gateway’s  default  IP  address: 
192.168.99.100. 
5.  Energize the +24Vdc supply attached to the 
Manager Gateway. 
NOTE 
Be sure the computer or network switch is 
powered on before the Manager Gateway. 
Failure to power up the Manager Gateway 
before it is attached to an energized network 
will result in failure of the Manager Gateway 
Ethernet communications. The correct power 
up sequence must be used. 
6.  Verify  you  can  successfully  ping  (command 
executed at the Windows command prompt) 
the  Manager  Gateway  to  validate  Ethernet 
communication. 
7.  Launch  the  Embedded  webpage  on  the 
Manager Gateway (Admin Toolset) by typing 
the  following  in  the  Internet  Explorer  menu 
bar: http://192.168.99.100. 
8.  Click  the  Yes  button  if  the  Security  Alert 
window  appears.  Sign  in  using  the  default 
user name: system and password: system
9.  Click Interfaces. Select either DHCP or Static 
IP  address  type.  Assign  a  valid  IP  Address, 
Subnet  Mask  and  Default  Gateway  for  the 
network  the  Manager  Gateway  will  reside 
on. Click Apply Changes