Essence Security International ltd. ES7000EG Manual De Usuario
Operation
52
EverGuard Control Panel
5. Under Power, set the indicators that notify the monitoring station of power
failure for the following parameters:
Random time for 220v fail indication – Enables or disables the
random time message that is sent to the monitoring station. This sends a
message at random time intervals to the monitoring station along with
the fixed time message. For multiple panels (e.g., in an apartment
building), it is recommended to set random time to send a message.
message at random time intervals to the monitoring station along with
the fixed time message. For multiple panels (e.g., in an apartment
building), it is recommended to set random time to send a message.
220v indication delay timeout – Defines the fixed time message to be
sent (in minutes). The master clock, after a delay, sends a message to
the monitoring station regarding a power failure.
the monitoring station regarding a power failure.
Range limit for 220v fail Random - Sets the random message to be
sent (in minutes). This parameter can only be configured if the Random
time for 220V fail indication parameter is enabled. It is recommended
to set this parameter for the value of that set for Random time for
220v fail indication + an additional 5 min.
time for 220V fail indication parameter is enabled. It is recommended
to set this parameter for the value of that set for Random time for
220v fail indication + an additional 5 min.
6. Press the Automatic Configuration button to set the automatic RF output
activation in each of the following system states:
ALARM
PANIC
ARM
DISARM
DURESS
From the Device dropdown list, select one of the following:
X-10 devices - can handle stronger appliances (e.g., washing machine,
etc.)
RF Output devices - generally is set for lights. Assign assigned an ID
number. The range is 1 to 16.
7. Under Password, configure the following codes:
Duress Pin-Code – Enter a 4 digit code to trigger dispatching a duress
message to the control center.
ESI-CMS DTMF Code – Enter a 4 digit code to activate external devices.
8. Localization – Set the source for the control panel real-time-clock. Select
enable to sync with the GSM network clock or disable to sync with the
monitoring station server.
For compliance with the EN 50131 standard, set Synchronize Clock from
GSM to enable.
The Panel local Time parameters are read-only and are drawn from the
system.
monitoring station server.
For compliance with the EN 50131 standard, set Synchronize Clock from
GSM to enable.
The Panel local Time parameters are read-only and are drawn from the
system.
9. Set the Periodic Test Period, in days, hours, minutes, how often the system
should send a test message to the control center.
Note that for compliance with the EN 50131 standard, this test should be
enabled and set to a period of not more than 2 hours.
enabled and set to a period of not more than 2 hours.
10. Set the Transmitter parameters according to requirements:
GSM Module – Enables or disables the GSM module.