Installation of Accessories
Scroll through the settings until you see MultiTank System. Press the CHECK MARK  
button and then use the UP ARROW or DOWN ARROW key to change from 
SINGLE to PROGRESSIVE flow. Press the CHECK MARK button when done.
NOTE: all multi tank systems are to be set to PROGRESSIVE. See below on adjust-
ments needed for alternating or parellel operation.
Press the CHECK MARK button and then use the UP or DOWN arrow keys to set the 
progressive flow trip point. Press the CHECK MARK button when done.
This setting establishes a flow rate which, when attained, will cause another unit to come on-line until the total flow 
rate is less than the established trip point for 30 seconds. Should the flow demand exceed the trip point by a rate 
equal to or greater than two times the trip point, another unit shall be brought on-line (assuming the system has 
more than two units in total). Each subsequent equivalent increase in flow demand shall continue to bring addi-
tional units on line (up to six total units if the flow demand is six times the TRIP amount). Units shall be returned 
to a stand-by mode in the reverse order as the system flow decreases by a rate equal to or greater than the trip 
point. Generally, the trip point is the rated continuous flow rate of one unit. These values can be found in the unit’s 
instruction manual.
NOTE: ALTERNATING OPERATION: To set up the GBE for alternating operation (one on, the rest standby), set the 
trip point to 999. It is unlikely that the system will reach 999 gallons per minute to bring on an additional unit.
In a multi-tank system, one unit must be specified as master. All other units are slaves. 
For example, in a triplex system, select one unit to be the master and set this setting to 
MASTER. In the 2nd unit, set this to SLAVE 1. In unit 3, set it to SLAVE 2. You can 
have up to 5 slaves connected to a master.
NOTE: PARALLEL OPERATION: To set up the GBE for parallel operation (all online), set the trip point to zero (0). 
As long as the flow is above zero, all units will stay online.
You must also set the jumpers as explained on page 12 for progressive flow.
Flow meters are required for progressive flow – one for each unit. See page 14 to set up the meters.
Continue pressing the down key to cycle through the rest of the options (refer to page 29). At the System Setup 
screen press the “X” key to return to the main screen.
NOTE: You must repeat this programming on all other units in the system. On slave units the PROG FLOW TRIP 
can be IGNORED; the only trip point recognized is the one set on the master unit.
Brine Reclaim
For brine reclaim, AUX OUT 2 and AUX OUT 3 must be set to open and close the valves to direct the brine. 
There are 4 things to set for each aux output.
1 –  Cycle Type (AUX X CYCLE TYPE) – can be set to NORMALLY ON or NORMALLY OFF. For brine 
reclaim, set it to NORMALLY OFF.
2 –  Cycle Position (AUX OUT X) – Any cycle position can be selected here. For brine reclaim, we want the 
BRINEDRAW POS.
3 –  Delay (AUX OUT DELAY) – This is the delay before the OUTPUT is “activated” in minutes. For brine reclaim 
we want delay on AUX 3 and no delay on AUX 2.
4 –  On time (AUX OUT ON) – This is the number of minutes the OUTPUT is “activated”  in minutes. For brine 
reclaim, cycle type is NORMALLY OFF so this is the amount of time the Aux contact is on.
multitank system
progressive
prog Flow trip
210 GPM
progress flow master
 