KROHNE FMCW06G10 Manual De Usuario

Descargar
Página de 76
 DESCRIPTION OF HART INTERFACE 
9
59
OPTIWAVE 1010
www.krohne.com
09/2014 - 4003537401 - MA OPTIWAVE 1010 R01 en
• Burst Mode is not supported
There are two ways of using the HART
®
 communication:
• as Point-to-Point connection and
• as Multi-Drop connection with 2-wire connection.
9.3.1  Point-to-Point connection - analogue / digital mode
Point-to-Point connection between the signal converter and the HART
®
 Master.
The current output of the device is passive.
Also.
9.3.2  Multi-Drop connection (2-wire connection)
Up to 15 devices may be installed in parallel (this signal converter and other HART
®
 devices).
For an illustration of multi-drop networks.
For data on communication in multi-drop mode.
9.4  HART
®
 device variables
The HART® dynamic variables PV (Primary Variable), SV (Secondary Variable), TV (Third Variable) 
and 4V (Fourth Variable) can be assigned to any of the device variables.
The HART
®
 dynamic variable PV is always connected to the HART
®
 current output which is, for 
example, assigned to level measurement.
9.5  Field Communicator 375/475 (FC 375/475)
The Field Communicator is a hand terminal from Emerson Process Management that is 
designed to configure HART
®
 and Foundation Fieldbus devices. Device Descriptions (DDs) are 
used to integrate different devices into the Field Communicator.
9.5.1  Installation
System and software requirements for the Field Communicator
• System card that includes the "Easy Upgrade Option"
• Field Communicator Easy Upgrade Programming Utility
• HART
®
 Device Description file
For more data, refer to the Field Communicator User’s Manual.
CAUTION!
The Field Communicator cannot be used to correctly configure, operate or read data from the 
device unless the Device Description (DD) file is installed.