KROHNE FMCW06G10 Manual De Usuario

Descargar
Página de 76
9
 DESCRIPTION OF HART INTERFACE 
60 
OPTIWAVE 1010
www.krohne.com
09/2014 - 4003537401 - MA OPTIWAVE 1010 R01 en
9.5.2  Operation
The Field Communicator and the device's local display use almost the same procedures to 
operate the signal converter. The online help for each menu item refers to the function number 
given to each menu item on the local device display. Protection of settings is the same as on the 
device's local display.
The Field Communicator always saves a complete configuration for communication with AMS.
For more data, refer to 
HART
®
 menu tree for Basic-DD on page 62.
9.6  Asset Management Solutions (AMS)
The Asset Management Solutions Device Manager (AMS) is a PC program from Emerson 
Process Management which is designed to configure and manage HART
®
, PROFIBUS and 
Foundation-Fieldbus devices. Device Descriptions (DDs) are used to integrate different devices 
into the AMS.
9.6.1  Installation
Please read the README.TXT file in the Installation Kit.
If the Device Description has not been installed at this time, install the Installation Kit HART
®
 
AMS. This .EXE file is given on the DVD-ROM supplied with the device. You can also download the 
file from our website.
For installation data, refer to the "AMS Intelligent Device Manager Books Online" section "Basic 
AMS Functionality > Device Configurations > Installing Device Types > Procedures > Install 
device types from media".
9.6.2  Operation
9.6.3  Parameter for the basic configuration
Due to AMS requirements and conventions, there are differences when operating the signal 
converter with AMS and operating using the local keyboard. The service menu parameters are 
not supported and simulation is only possible for current outputs. The online help for each 
parameter contains its function number as a reference to the local device display.
INFORMATION!
The Field Communicator will not give you access to the service menu. A simulation is only 
possible for current outputs.
INFORMATION!
For more data, refer to HART
®
 menu tree for AMS on page 62
.