Wiegand Connections
Wiegand output lines should be connected to the Wiegand compatible
controller.  When connecting Wiegand output to a controller, you must make that
connection using Data0, Data1, and a common Ground reference.  Wiegand
input lines can be used for an alternate Wiegand input device (this connection is
required for the V-Flex device).
ESD Shield Earth Ground Requirement
The Finger mask (conductive plastic surrounding the fingerprint sensor) is
sometimes referred to as an ESD Shield.  Pin 15 on the Pigtail (EGRND on the
input/earth-ground connector for V-Station) is connected to the ESD shield of the
fingerprint sensor.  This should be connected in such a way as to make a low-
impedance connection to Earth ground.  DO NOT CONNECT THE SHIELD TO
POWER GROUND.  Improper connections will potentially create ground loops that
may cause damage to the Veri-Series and other equipment.  Furthermore,
neglecting to provide a path for ESD to Earth ground puts the electronics at risk if
ESD is discharged into the unit from a user.
RS-485
RS-232 and RS-485 are used for communication with a PC running Veri-Series
compatible software (such as our VeriAdmin software). RS-485 connections
among various readers should be made by connecting the (+) and (-) lines of the
differential RS-485 in a daisy chain manner.  For instance, from V-Prox to V-Prox,
the (+) line from one V-Prox is connected to the (+) line of the next V-Prox and so
on; likewise for the (-) lines.  Additionally, connect the grounds from each V-Prox
unit back to the signal ground connection for the PC.
Ethernet (V-Station only)
The RJ-45 Ethernet connector can also be used for communication with a PC
running Veri-Series compatible software (Version 5.10 and above).  Standard
Ethernet patch cables may be used, but care must be taken to identify straight-
through cables versus crossover cables.  To wire a V-Station directly to a PC NIC
card, a crossover cable must be used.  For connecting multiple V-Stations
together on an Ethernet bus or directly to a switch or hub, straight-through cables
should be used.
TTL (V-Station only)
The TTL Input/Output connections are standard 5V TTL Logic lines and are reserved
for future use.