Cabling and Interconnection
Cabling may seem to be a trivial aspect to the installation, requiring nothing more
than planning the cabling route and pulling the cable through the building.  This is
true for Wiegand and power wiring considerations, however, if your installation
requires the use of RS-485 or Ethernet communications, then the choice of cable,
the cable run length, the network topology, and termination of the network may
be very important aspects that must not be overlooked.
Parameter
10 Mbps
100 Mbps
1000 Mbps
Maximum collision diameter,
DTE to DTE
328 ft. UTP
328 ft. UTP
1352 ft. fiber
328 ft. UTP
1037 ft. fiber
Maximum collision diameter
with repeaters
8202 ft.
673 ft.
656 ft.
Maximum number of
repeaters in network path
5
2
1
Maximum number of devices
on one line
255
255
255
Maximum Data Rate*
*V-Station supports only 10BaseT (10 Mbps); internally,
the product is still limited to 56K or 115K bps
Spec
RS-485
RS-232
Mode of Operation:
Differential DC
Coupled
Single-ended DC Coupled
DC Isolation:
No
No
Max. Distance:
4000 ft.
200 ft.*
Number of Devices on
one line:
32
2
Max. Data Rate
56 kbps
56 kbps*
*RS-232 communications distances are dependent on baud rate (bps).  For
example, at 9600 baud, a distance of 100 ft. is possible with shielded cable, but at
56 k-baud (kbps) a maximum of 20 ft. is recommended.
Table 5: RS-232 / RS-485 Communications Comparison
Table 6: Ethernet Comparison