Section 4 Network Turnup Procedure
612806320L1-1A
Copyright © 2005 ADTRAN, Inc.
49
to the product at the terminal provided, and shall be connected to ground in a manner that will retain the
ground connection when the product is unplugged from the receptacle. The connection to ground of the
supplementary equipment grounding conductor shall be in compliance with the rules for terminating
bonding jumpers at Part K or Article 250 of the National Electrical Code, ANSI/NFPA 70. Termination of
the supplementary equipment grounding conductor is permitted to be made to building steel, to a metal
electrical raceway system, or to any grounded item that is permanently and reliably connected to the
electrical service equipment ground.
ground connection when the product is unplugged from the receptacle. The connection to ground of the
supplementary equipment grounding conductor shall be in compliance with the rules for terminating
bonding jumpers at Part K or Article 250 of the National Electrical Code, ANSI/NFPA 70. Termination of
the supplementary equipment grounding conductor is permitted to be made to building steel, to a metal
electrical raceway system, or to any grounded item that is permanently and reliably connected to the
electrical service equipment ground.
The supplemental grounding conductor shall be connected to the equipment using a number 8 ring terminal
and should be fastened to the grounding lug provided on the rear panel of the equipment. The ring terminal
should be installed using the appropriate crimping tool (AMP P/N 59250 T-EAD Crimping Tool or
equivalent.)
and should be fastened to the grounding lug provided on the rear panel of the equipment. The ring terminal
should be installed using the appropriate crimping tool (AMP P/N 59250 T-EAD Crimping Tool or
equivalent.)
6.
SUPPLYING POWER TO THE UNIT
The TRACER 6200 can operate from a supply between 21 and 60 VDC, with either polarity referenced to
ground. Power supplies should be able to provide up to 25 Watts at the selected voltage. A dual pin
terminal plug accepts power at the rear panel of the unit, providing a voltage (
ground. Power supplies should be able to provide up to 25 Watts at the selected voltage. A dual pin
terminal plug accepts power at the rear panel of the unit, providing a voltage (
+/–
) and ground (
GND
)
reference point.
7.
MOUNTING OPTIONS
Indoor Unit (IDU)
Install the TRACER 6200 in a location that requires minimal feedline length. The TRACER 6200 is
designed to be mounted in a rack. If multiple units are installed in one location, one-half inch of spacing is
recommended above and below the unit.
designed to be mounted in a rack. If multiple units are installed in one location, one-half inch of spacing is
recommended above and below the unit.
The TRACER 6200 systems are 1U high, rack-mountable units which can be installed into 19- inch (see
Figure 2 on page 50) or 23-inch (see Figure 3 on page 51) equipment racks using the supplied rackmount
The supplemental equipment grounding terminal is located on the rear panel of the
TRACER 6200.
TRACER 6200.
•
This unit shall be installed in accordance with Article 400 and 364.8 of the
NEC NFPA 70 when installed outside of a Restricted Access Location (i.e., central
office, behind a locked door, service personnel only area).
office, behind a locked door, service personnel only area).
•
Power to the TRACER 6200 DC system must be from a reliably grounded
21 to 60 VDC UL Listed or CSA Certified ITE Power Supply with outputs meeting LPS
requirements.
requirements.
•
A readily accessible disconnect device that is suitably approved and rated shall be
incorporated in the field wiring.
incorporated in the field wiring.