Adtran TRC6320 Manual Do Utilizador

Página de 128
TRACER 6000 Series Split System Manual
Section 4  Network Turnup Procedure
612806320L1-1A
Copyright © 2005 ADTRAN, Inc.
49
to the product at the terminal provided, and shall be connected to ground in a manner that will retain the 
ground connection when the product is unplugged from the receptacle. The connection to ground of the 
supplementary equipment grounding conductor shall be in compliance with the rules for terminating 
bonding jumpers at Part K or Article 250 of the National Electrical Code, ANSI/NFPA 70. Termination of 
the supplementary equipment grounding conductor is permitted to be made to building steel, to a metal 
electrical raceway system, or to any grounded item that is permanently and reliably connected to the 
electrical service equipment ground.
The supplemental grounding conductor shall be connected to the equipment using a number 8 ring terminal 
and should be fastened to the grounding lug provided on the rear panel of the equipment. The ring terminal 
should be installed using the appropriate crimping tool (AMP P/N 59250 T-EAD Crimping Tool or 
equivalent.)
6.
SUPPLYING POWER TO THE UNIT
The TRACER 6200 can operate from a supply between 21 and 60 VDC, with either polarity referenced to 
ground. Power supplies should be able to provide up to 25 Watts at the selected voltage. A dual pin 
terminal plug accepts power at the rear panel of the unit, providing a voltage (
+/–
) and ground (
GND
reference point.
7.
MOUNTING OPTIONS
Indoor Unit (IDU)
Install the TRACER 6200 in a location that requires minimal feedline length. The TRACER 6200 is 
designed to be mounted in a rack. If multiple units are installed in one location, one-half inch of spacing is 
recommended above and below the unit.
The TRACER 6200 systems are 1U high, rack-mountable units which can be installed into 19- inch (see
 
Figure 2 on page 50) or 23-inch (see Figure 3 on page 51) equipment racks using the supplied rackmount 
The supplemental equipment grounding terminal is located on the rear panel of the 
TRACER 6200.
This unit shall be installed in accordance with Article 400 and 364.8 of the
 
NEC NFPA 70 when installed outside of a Restricted Access Location (i.e., central 
office, behind a locked door, service personnel only area).
Power to the TRACER 6200 DC system must be from a reliably grounded 
 
21 to 60 VDC UL Listed or CSA Certified ITE Power Supply with outputs meeting LPS 
requirements.
A readily accessible disconnect device that is suitably approved and rated shall be 
incorporated in the field wiring.