Supervised Wireless PowerCode Smoke Detector 
 
Installation Instructions 
 
 
1. INSTALLATION SUMMARY 
1.1 Disassembly 
A.  Separate the unit from its mounting bracket as shown in 
Figure 1. 
 
Figure 1. Separating the MCT-423 from its Bracket 
B.  Open the MCT-423 by pulling the cover away from the base 
at the point indicated by “OPEN HERE” in Figure 2. 
 
Figure 2. MCT-423 with Cover Swung Open
 
1.2 Setting the Function Switch 
The MCT-423 has a 4-position DIP switch function selector (see 
Figure  3).  The switch levers are numbered 1 to 4, and each 
switch allows you to select one of two options.
  
Open the cover and set the function switches as desired. The ON 
position is indicated by the arrow near the switch body. 
Table 1. Function selector settings 
Sw- 
Marking  Pos.  Selected Option 
Defaul
t
 
SW-1  LED 
ON 
OFF 
LED will light upon transmission 
LED is disabled 
ON 
SW-2  RESTORE ON 
OFF 
“Restore” events reported 
“Restore” events not reported 
ON 
SW-3  TR-REP 
ON 
OFF 
Alarm reported every 3 min . 
Alarm reported only once 
OFF 
SW-4  BAT  
ON 
OFF 
Lithium battery is being used 
Alkaline battery is being used 
OFF 
Note: Transmissions initiated by “tamper” events will be repeated 
once every 3 minutes, regardless of SW-3 setting
 
Figure 3. Transmit Indicator and Function Switch 
1.3 Battery Connection and Initial Test 
CAUTION: The MCT-423 comes with cover latches that will 
prevent the cover from closing if there is no battery 
inside. 
 
The smoke detector is supplied with a 9V alkaline battery seated 
within its holder but insulated from the battery terminals.  
A.  Pull the battery out and peel off the insulating material to 
expose the terminals. 
B.  Match the battery terminals with the flexible contacts on the 
detector PCB. Be sure to get the polarity right.  If you 
reverse the [+] and [–], the battery will discharge 
completely within a very short time through the built in 
protection diode!  
 
C.  When the terminals are properly matched, push the battery 
firmly in until it is seated tightly within the holder. 
 
Note: When the battery first makes contact with the detector, 
the alarm horn may sound for one second. This indicates that 
the battery is positioned properly.  
D.  Close the cover, then press the test button for about 5 
seconds until the horn sounds two sequences of a loud 3-
beep alarm.  This means that the smoke detection 
section is working properly.  
1.4 Resetting the Transmitter Module and Enrolling 
its PowerCode ID 
A tamper protection switch is 
mounted on the transmitter 
board. The tamper actuator, 
extending through a hole in the 
base (see Figure 4), is pressed 
against the bracket when the 
unit is attached to the bracket. 
Removal of the unit from the 
bracket will cause the switch 
contacts to open, creating a 
tamper event, which will be 
reported by the transmitter to 
the control panel. 
 
Figure 4. Tamper Switch