Visonic Inc. MCT423 Manual De Usuario

Descargar
Página de 8
2
 
DE3640
 
Besides its tamper protection role, the tamper switch is 
used to reset the transmitter at power up  - this is 
important for proper function of the unit. 
To reset the transmitter and enroll its ID in the control panel’s 
memory, proceed as follows: 
A.  Close the cover and turn the unit over, so that you can see 
the back of the base. 
B.  Press the tamper switch once and release it. This will perform 
the reset necessary for smooth transmitter power-up. 
C.  Refer to the control panel’s installation instructions and follow 
the procedure given there for enrolling transmitter IDs. When 
required to initiate a transmission for enrollment, press the 
smoke detector’s test button until the built-in horn sounds. 
Note: It is much easier to carry out this operation while holding 
the MCT-423 in your hand, close to the control panel.
 
1.5 Mounting the Bracket in Place 
Read Section 4 in this manual first, then decide where to install a 
detector. Refer to Figures 5 and 6 and proceed as follows: 
  
Figure 5. Aligning the Bracket
 
 
Figure 6. Mounting the 
Bracket
 
1st.At the chosen location, draw a 15 cm (6”) long horizontal line. 
2nd.Press the bracket against the mounting surface, aligning the 
two longest keyhole slots with the line drawn in Step A. Mark 
the drilling spots through two opposite keyhole slots.  
C.  Drill two 5 mm (3/16”) holes at the marked spots. 
D.  Attach the bracket to the wall, using the two screws and 
plastic wall anchors (supplied). 
1.6 Final Assembly and Test 
1st. Before attaching the detector unit to the bracket, it is a good 
practice to secure the cover to the base with two screws 
(supplied with the unit) through the holes shown in Figure 7. 
This will prevent unauthorized opening of the cover.