Digital Monitoring Products Inc PC0124 Manual De Usuario

Descargar
Página de 4
1105 Installation Guide 
Digital Monitoring Products
3
1105 External Contact Mounting
When connecting an external contact to the terminal block, DMP recommends using 18 or 22-gauge unshielded wire.
Do not use twisted pair or shielded wire. Connect the external contact as normally open (N/O) or normally closed 
(N/C) without any end-of-line resistor. Refer to the Contact option under Zone Information in the appropriate panel 
programming guide.  
Note: When using both the internal reed switch and external terminal block, you must use consecutive zone 
numbers.  Refer to the following examples:
XR500 system — zones 562 and 563 or zones 893 and 894
XR100 system — zones 523 and 524 or zones 593 and 594
XT30/XT50 Series — zones 31 and 32 or zones 34 and 41
Figure 7: External Contact Wiring
Magnet
1105 Universal
Transmitter
External
Contact
External Contact
Terminal Block
Internal Contact
Reed Switch
Internal Contact Magnet
External Contact
Program External
Contact as next 
consecutive Zone
Program 
Internal
Contact 
as one Zone
Window
Door
1105-EOL Wiring and Connecting Contacts 
When connecting an external contact to the terminal block, DMP recommends using 18 or 22-gauge unshielded wire.
Do not use twisted pair or shielded wire. Connect the contact as normally open (N/O) or normally closed (N/C) with the
470K end-of-line resistor as shown in Figure 8.
Note:  The Normally Open YES NO option in the panel wireless zone programming has no affect on the transmitter 
operation when using the 470K end-of-line resistor.
Installing or Replacing the Battery
Observe polarity when installing the battery. Use only 3.0V lithium batteries, DMP Model CR123, or the equivalent
battery from a local retail outlet. For UL installations, only use #123 batteries manufactured by Energizer for the
1105 or CR123A batteries manufactured by Panasonic for the 1105-EOL.
Note: When setting up a wireless system, it is recommended to program zones and connect the receiver before 
installing batteries in the transmitters.
1. If installed, remove the transmitter housing cover as shown in Figure 1.  
2. If replacing the battery, remove the old battery and dispose of it properly.
3. Place the 3.0V lithium battery in the holder as shown in Figure 2 and press into place.
4. Align the back of the transmitter cover next to the battery and snap the cover into place.
  Caution: Risk of fire, explosion, and burns. Do not recharge, disassemble, heat above 212°F (100°C), or 
 
incinerate.  Properly dispose of unused batteries.
External Contact
Program Contact in 
Panel Zone Programming
Contact
Terminal
Block
470K
470K
Series for N/C
Parallel for N/O
Figure 8: Contact Terminal Block Wiring