37
ZONE INFORMATION
condition. The output can be activated regardless of the report to transmit
or whether or not the zone is programmed as local. An output activated by a
non-24-hour armed zone is turned off when the zone’s area is disarmed by a user.
To enter an Output Number, press any select key followed by the output number
51-54, 61-64, or F1-F20. Press the COMMAND key.
33.11.3
Output Action
Entering an Output Number displays this option that allows you to assign an output
action. A description of the available output actions is given below:
STEADY - The output is turned on and remains on until the area is disarmed, an
output cutoff time expires, or the output is reset from the keypad User Menu.
PULSE - The output alternates one second on and one second off until the area is
disarmed, an output cutoff time expires, or the output is reset from the keypad
User Menu.
MOMENTARY - The output is turned on only once for one second.
FOLLOW - The output is turned on and remains on while the zone is in an off
normal, or bad condition. When the zone restores, the output is turned off.
After you have selected the Message To Transmit, the display prompts you for
the same three selections for Disarmed Short, Armed Open, and Armed Short
conditions. If the zone is a 24-hour type, only the Armed Open and Armed Short
conditions are displayed. When you have programmed all of the zone conditions,
the Swinger Bypass selection is then dis played.
33.12
Swinger Bypass
Selecting YES allows the zone to be swinger bypassed by the panel according to
the programming in Swinger Bypass Trips and Reset Swinger Bypass. The Bypassed
zone displays in the keypad Status List. Selecting NO disables swinger bypassing for
this zone.
How it works
If within one hour, a zone trips the total number of times as specified in Swinger
Bypass Trips, the panel bypasses it until the following conditions occur; the area
in which the zone is assigned is disarmed, the zone is manually reset through the
Bypass Zones keypad User Menu function, the zone remains normal for one hour
and the Reset Swinger Bypass is YES.
If the zone trips fewer than the specified times within one hour of the first trip,
the bypass trip counter returns to 0 (zero) and the process must be repeated.
A report of the swinger bypass is sent to the receiver if Bypass Reports is YES.
33.13
Prewarn Address
Option is only shown for an Exit zone.
At the start of the entry delay, all keypad addresses dis play ENTER CODE:-. If you
want the prewarn to sound at all addresses, leave the default as shown.
To delete an address, press the matching number on the keypad. To disable
prewarning at all keypads, press a top row key to clear the addresses shown. Press
the COM MAND key when the address selection is com plete.
Note: The prewarn tone stops at the keypad when the first digit of a user code is
entered. If, within five seconds, a valid user code is not entered or an invalid user
code is entered, the prewarn tone begins sounding again. Fifteen seconds must
elapse before entering a digit silences the prewarn tone again.
33.14
Entry Delay
Option is only shown for an Exit zone. Select the entry delay timer for this
zone. Entry delay timers 1 and 2 are programmed in Entry Delay in the System
Options menu.
33.15
Cross Zone
Select
YES to enable cross-zoning for this zone. Cross-zoning requires this zone to
trip twice, or this zone and another cross-zoned zone to trip, within a programmed
time before an alarm report is sent to the receiver.
Note: To operate correctly, all cross-zone zones need to be programmed as the
same zone type.
When a cross-zoned zone trips, the Output action assigned to the zone activates.
See the Bell Action section. The cross-zone time specified in System Options begins
to count down. See the Cross-Zone Time section. If another cross-zoned zone in the
system faults, or if the first zone restores and faults again before the cross-zone time
expires, the bell turns on and the panel sends an alarm report.
If no other cross-zoned zone in the system trips before the cross-zone time expires,
ACTION:
STD PLS MOM FOLW
SWGR BYP NO YES
PREWARN: 12345
ENTRY DELAY:
1
CRS ZONE NO YES