T
C F
SET THE DIP SWITCHES
4
 1115 INSTALLATION GUIDE     |     DIGITAL MONITORING PRODUCTS    
                       2 
SELECT A LOCATION
The 1115 provides a survey capability to allow one person 
to confirm communication with the wireless receiver or 
panel while the cover is removed. This allows you to easily 
determine the best location for the 1115. Be sure to choose a location 
on a flat wall or single‑gang box away from large metal objects.
1.  Hold the 1115 in the exact desired location.
2. Press the tamper switch to send data to the receiver and  
determine if communication is confirmed or faulty. See Figure 
2 for tamper switch and LED locations.
Confirmed: If communication is confirmed, the survey 
LED turns on when data is sent to the receiver and off 
when acknowledgement is received. 
Faulty: If communication is faulty, the LED remains on 
for about 8 seconds or flashes multiple times in quick 
succession. 
3. Relocate the 1115 or receiver until the LED confirms clear 
communication. Proper communication between the 1115 
and receiver is verified when for each press or release of 
the tamper switch, the LED blinks immediately on and 
immediately off.
3
The 1115 has four DIP switches (labeled 1 through 4) located on the PCB. Cold and flood settings can 
be turned on or off. Hot/warm and freeze/refrigerate are either‑or settings. Refer to Table 1 for DIP 
switch setting options and operations:
OPERATION
DIP SWITCH 
POSITION
CONTACT
ALARM OCCURS  
WHEN:
ZONE RESTORES  
WHEN:
SENSOR 
Cold
1 = ON
1
Temperature drops below 45ºF for 
>10 minutes
Temperature rises above 48ºF 
for > 4 minutes
Internal
Hot
2 = OFF
Temperature rises above 95ºF for 
> 10 minutes
Temperature drops below 
92ºF for > 4 minutes
Internal
Warm
2 = ON
2
Temperature rises above 75ºF for 
> 10 minutes
Temperature drops below 
72ºF for > 4 minutes
Internal
Freezer
3 = OFF
3
Temperature rises above 10°F for 
> 30 minutes
Temperature drops below 7°F 
for > 4 minutes
External (T280R)
Refrigerator
3 = ON
3
Temperature rises above 42°F for 
> 30 minutes
Temperature drops below 
39°F for > 4 minutes
External (T280R)
Flood
4 = ON
4
Probe tips are in contact with 
water for > 3 minutes
Probe tips have not been in 
water for > 3 minutes
External (470PB)
Survey 
LED
Tamper 
Switch
Figure 2:  Tamper Switch and 
Survey LED
Table 1: DIP Switch Settings and Operation