16
Programming
To set No Activity Time-out, press:
Add—Option #—15—02 - 24—DONE.
To turn off No Activity Time-out, press:
Delete—Option #—15—DONE.
Option 16: Auto Phone Test (Default = off)
Determines whether the panel automatically performs a peri-
odic phone test (on) or not (off).
The test interval can be from 001 - 254 days. Entries must be 3 
digits. The time of day the panel performs the test is deter-
mined by Option 72: Supervisory Time, which must be turned 
on for this feature to work.
Note 
For UL 1635 listed systems, Auto Phone Test must be set 
to 001 days.
To set Auto Phone Test, press:
Add—Option #—16—001 - 254—DONE.
To turn off Auto Phone Test, press:
Delete—Option #—16—DONE.
Option 17: Dialer Delay (Default = off)
Determines whether the panel delays dialing programmed 
phone numbers before sending reports (on), or if dialing begins 
immediately (off).
If Option 21: Opening (Disarming) Reports is on, the panel 
does not delay dialing if the system is disarmed before the 
delay time expires. The panel dials immediately for both the 
alarm and opening report.
Note 
Regardless of this option setting, the panel always dials 
immediately for alarms from sensors in groups 0-8, 26, 
for alarms triggered by the control panel or remote hand-
held touchpad emergency buttons, and for programming, 
AC power failure, and low battery reports.
The delay time can be set from 005 - 254 seconds (015 to 045 
if Option 69: SIA Limits is on). Entries must be 3 digits.
Note 
For UL installations, the Dialer Delay must not exceed 45 
seconds.
To set Dialer Delay, press:
Add—Option #—17—005 - 254—DONE.
To turn off Dialer Delay, press:
Delete—Option #—17—DONE.
Option 18: Alarm Cancel Report (Default = 005 
minutes)
Sets the time frame that determines whether the panel reports 
an alarm cancel message to the central station.
If the system is disarmed from an alarm state within the pro-
grammed time, the panel sends an alarm cancel message to the 
central station. An alarm cancel message is not reported if the 
system is disarmed after the programmed time expires.
The time can be set from 005 - 255 minutes. Entries must be 3 
digits. When set to 255, the panel always reports alarm cancel 
messages. Turning off this option disables alarm cancel report-
ing.
To turn on Alarm Cancel Report, press:
Add—Option #—18—005 - 255—DONE.
To turn off Alarm Cancel Report, press:
Delete—Option #—18—DONE.
Option 19: RF Timeout (Default = 12 hours)
Determines the time period the panel must receive at least one 
supervisory signal from learned sensors before identifying a 
sensor failure and sounding trouble beeps. Any sensor failure 
is reported immediately and again at the supervisory time 
(Option 72: Supervisory Time).
The timeout can be set from 02-24 hours. Entries must be 2 
digits.
Note 
Setting this feature to 2 hours (02) may cause false 
reports.
For UL 985 and 1635 listed systems, RF Timeout must 
be set to 4 hours (04). For UL 1023 listed systems, RF 
Timeout must be set to 24 hours (24).
To change RF Timeout, press:
Add—Option #—19—02 - 24—DONE.
To reset RF Timeout (return to default), press:
Delete—Option #—19—DONE.
Option 20: Manual Phone Test (Default = on)
Determines whether the user can perform a manual phone test 
to verify communication to a central station/pager (on), or not 
(off).
To turn on Manual Phone Test, press:
Add—Option #—20—DONE.
To turn off Manual Phone Test, press:
Delete—Option #—20—DONE.