UTC Fire & Security Americas Corporation Inc 787E-SIMON Manual De Usuario
16
Programming
To set No Activity Time-out, press:
Add—Option #—15—02 - 24—DONE.
To turn off No Activity Time-out, press:
Delete—Option #—15—DONE.
Option 16: Auto Phone Test (Default = off)
Determines whether the panel automatically performs a peri-
odic phone test (on) or not (off).
odic phone test (on) or not (off).
The test interval can be from 001 - 254 days. Entries must be 3
digits. The time of day the panel performs the test is deter-
mined by Option 72: Supervisory Time, which must be turned
on for this feature to work.
digits. The time of day the panel performs the test is deter-
mined by Option 72: Supervisory Time, which must be turned
on for this feature to work.
Note
For UL 1635 listed systems, Auto Phone Test must be set
to 001 days.
to 001 days.
To set Auto Phone Test, press:
Add—Option #—16—001 - 254—DONE.
To turn off Auto Phone Test, press:
Delete—Option #—16—DONE.
Option 17: Dialer Delay (Default = off)
Determines whether the panel delays dialing programmed
phone numbers before sending reports (on), or if dialing begins
immediately (off).
phone numbers before sending reports (on), or if dialing begins
immediately (off).
If Option 21: Opening (Disarming) Reports is on, the panel
does not delay dialing if the system is disarmed before the
delay time expires. The panel dials immediately for both the
alarm and opening report.
does not delay dialing if the system is disarmed before the
delay time expires. The panel dials immediately for both the
alarm and opening report.
Note
Regardless of this option setting, the panel always dials
immediately for alarms from sensors in groups 0-8, 26,
for alarms triggered by the control panel or remote hand-
held touchpad emergency buttons, and for programming,
AC power failure, and low battery reports.
immediately for alarms from sensors in groups 0-8, 26,
for alarms triggered by the control panel or remote hand-
held touchpad emergency buttons, and for programming,
AC power failure, and low battery reports.
The delay time can be set from 005 - 254 seconds (015 to 045
if Option 69: SIA Limits is on). Entries must be 3 digits.
if Option 69: SIA Limits is on). Entries must be 3 digits.
Note
For UL installations, the Dialer Delay must not exceed 45
seconds.
seconds.
To set Dialer Delay, press:
Add—Option #—17—005 - 254—DONE.
To turn off Dialer Delay, press:
Delete—Option #—17—DONE.
Option 18: Alarm Cancel Report (Default = 005
minutes)
Sets the time frame that determines whether the panel reports
an alarm cancel message to the central station.
an alarm cancel message to the central station.
If the system is disarmed from an alarm state within the pro-
grammed time, the panel sends an alarm cancel message to the
central station. An alarm cancel message is not reported if the
system is disarmed after the programmed time expires.
grammed time, the panel sends an alarm cancel message to the
central station. An alarm cancel message is not reported if the
system is disarmed after the programmed time expires.
The time can be set from 005 - 255 minutes. Entries must be 3
digits. When set to 255, the panel always reports alarm cancel
messages. Turning off this option disables alarm cancel report-
ing.
digits. When set to 255, the panel always reports alarm cancel
messages. Turning off this option disables alarm cancel report-
ing.
To turn on Alarm Cancel Report, press:
Add—Option #—18—005 - 255—DONE.
To turn off Alarm Cancel Report, press:
Delete—Option #—18—DONE.
Option 19: RF Timeout (Default = 12 hours)
Determines the time period the panel must receive at least one
supervisory signal from learned sensors before identifying a
sensor failure and sounding trouble beeps. Any sensor failure
is reported immediately and again at the supervisory time
(Option 72: Supervisory Time).
supervisory signal from learned sensors before identifying a
sensor failure and sounding trouble beeps. Any sensor failure
is reported immediately and again at the supervisory time
(Option 72: Supervisory Time).
The timeout can be set from 02-24 hours. Entries must be 2
digits.
digits.
Note
Setting this feature to 2 hours (02) may cause false
reports.
reports.
For UL 985 and 1635 listed systems, RF Timeout must
be set to 4 hours (04). For UL 1023 listed systems, RF
Timeout must be set to 24 hours (24).
be set to 4 hours (04). For UL 1023 listed systems, RF
Timeout must be set to 24 hours (24).
To change RF Timeout, press:
Add—Option #—19—02 - 24—DONE.
To reset RF Timeout (return to default), press:
Delete—Option #—19—DONE.
Option 20: Manual Phone Test (Default = on)
Determines whether the user can perform a manual phone test
to verify communication to a central station/pager (on), or not
(off).
to verify communication to a central station/pager (on), or not
(off).
To turn on Manual Phone Test, press:
Add—Option #—20—DONE.
To turn off Manual Phone Test, press:
Delete—Option #—20—DONE.