Unit Description, FCU-01
10
Unit Description, FCU-01
The Fan Control Unit (FCU) controls and supervises the fans in the
RBS 2206. It is the MMI for the fans, that is, it has indicators for fan
status information. The FCU is connected to the EPC-bus that handles
communication for the climate and power function in the RBS.
The interface towards the EPC-bus consists of an optical fibre interface.
The interface towards each fan consists of one variable DC voltage
output for the power feed and one alarm input.
10.1
Functions
The FCU receives information on the EPC-bus about the required DC
voltage level for each fan. It feeds each fan with the required DC
voltage level. If no DC level is received, the DC level for the fans will
be equal to the FCU input voltage, minus a maximum voltage drop of
0.7 V.
If the normally closed circuit in the fan is opened, the indicator "Fan
fault" for that fan is illuminated, and an alarm is sent through the
EPC-bus.
The FCU compares the DC level for each fan with the required DC
level. If these do not match, the indicator "FCU fault" is illuminated,
and an alarm is sent through the EPC-bus.
If the communication on the bus no longer is defined, the indicator "EPC
bus fault" is illuminated, and an alarm is sent through the EPC-bus.