X75 SERIES - Mk3 Controller
INSTALLATION & OPERATING MANUAL
Manual No. x75mk3-11
x75-man-Rev11-0815.indd
Outputs
K1-8 – Dry contact relays with changeover contacts. X75 uses K1-4 only.
MAJ LED – LED indicating a major alarm. This is the red LED on the front panel
MAJ LED – LED indicating a major alarm. This is the red LED on the front panel
display.
MIN LED – LED indicating a minor alarm. This is the yellow LED on the front
MIN LED – LED indicating a minor alarm. This is the yellow LED on the front
panel display.
ACF LED – LED indicating an AC Failure. This LED is not present on the controller.
RFA LED – LED indicating the failure of one or more rectifiers. This LED is not
ACF LED – LED indicating an AC Failure. This LED is not present on the controller.
RFA LED – LED indicating the failure of one or more rectifiers. This LED is not
present on the controller.
OTA LED – LED indicating an out of range temperature condition. This LED is
OTA LED – LED indicating an out of range temperature condition. This LED is
not present on the controller.
OVA LED – LED indicating an over voltage condition. This LED is not present
OVA LED – LED indicating an over voltage condition. This LED is not present
on the controller.
EMAIL – Any alarms connected to this output will generate an alert email message
EMAIL – Any alarms connected to this output will generate an alert email message
when this facility has been set up (see section 13.6 - Network Settings).
BUZ – Any alarms connected to this output will cause the internal audible alarm
BUZ – Any alarms connected to this output will cause the internal audible alarm
to sound.
13.5.2 - Temperature Alarms
Figure 24 - Alarm Matrix WEB Applet - temperature alarm settings (typical)
Battery Over Temperature – This alarm will be active when the battery temperature
exceeds the activation temperature. It will not deactivate until the temperature falls
below the cancellation temperature.
Battery Under Temperature – This alarm will be active when the battery temperature
Battery Under Temperature – This alarm will be active when the battery temperature
falls below the activation temperature. It will not deactivate until the temperature
rises above the cancellation temperature.
External Over Temperature – The alarm will be active when the external
External Over Temperature – The alarm will be active when the external
temperature exceeds the activation temperature. It will not deactivate until the
temperature falls below the cancellation temperature.