Unique Broadband Systems Ltd. DRU2KW User Manual

Page of 64
Page 43
X75 SERIES - Mk3 Controller
INSTALLATION & OPERATING MANUAL
Manual No. x75mk3-11
x75-man-Rev11-0815.indd
Outputs
K1-8 – Dry contact relays with changeover contacts.  X75 uses K1-4 only.
MAJ LED – LED indicating a major alarm.  This is the red LED on the front panel 
display.
MIN LED – LED indicating a minor alarm.  This is the yellow LED on the front 
panel display.
ACF LED – LED indicating an AC Failure.  This LED is not present on the controller.
RFA LED – LED indicating the failure of one or more rectifiers.  This LED is not 
present on the controller.
OTA LED – LED indicating an out of range temperature condition.  This LED is 
not present on the controller.
OVA LED – LED indicating an over voltage condition.  This LED is not present 
on the controller.
EMAIL – Any alarms connected to this output will generate an alert email message 
when this facility has been set up (see section 13.6 - Network Settings).
BUZ – Any alarms connected to this output will cause the internal audible alarm 
to sound.
13.5.2 - Temperature Alarms
Figure 24 - Alarm Matrix WEB Applet - temperature alarm settings (typical)
Battery Over Temperature – This alarm will be active when the battery temperature 
exceeds the activation temperature.  It will not deactivate until the temperature falls 
below the cancellation temperature.
Battery Under Temperature – This alarm will be active when the battery temperature 
falls below the activation temperature.  It will not deactivate until the temperature 
rises above the cancellation temperature.
External  Over Temperature  – The alarm will be active when the external 
temperature exceeds the activation temperature.  It will not deactivate until the 
temperature falls below the cancellation temperature.