Tecnoware UPS EXA 3.2 FGCEXA3K2 Prospecto

Los códigos de productos
FGCEXA3K2
Descargar
Página de 2
UPS Battery life in operating conditions
The higher is the temperature of the environment in which the
UPS works, the shorter is the battery life.
0
1
4
5
20
0
30
40
50
6
Battery life (years)
Temperature (C°)
25
35
45
3
2
1,5
40
60
80
100
0
6
9
12
5° C (41° F)
25° C (77° F)
30° C (88° F)
40° C (104° F)
UPS (with batteries) storage
Battery capacity (%)
Storage (months)
It is necessary to
recharge the batteries
for a minimum
of 24 hours.
Attention: batteries
may not be recoverable
even when subjected
to charging.
3
15
18
21
24
27
30
EASY INTERACTIVE
L
’A
Z
IE
N
D
A
UPS EXA 
1.1-1.5-2.2-2.6-3.2
Specifi cation
UPS Model  
EXA 1.1 
EXA 1.5 
EXA 2.2 
EXA 2.6 
EXA 3.2
Code 
FGCEXA1K1 FGCEXA1K5 FGCEXA2K2 
 FGCEXA2K6 FGCEXA3K2
Nominal power 
1100 VA 
1500 VA 
2200 VA 
2600 VA 
3200 VA
Active power 
550 W 
750 W 
1100 W 
1300 W 
1600 W
Power factor 
 
 
0.5
Technology 
 
 
Line Interactive with stabilizer
Cooling  
 
 
Natural
Audible noise 
 
 
< 40 dBA at 1 m
Dimension (UPS) WxHxD 
14,5x21,5x36 cm 
14,5x21,5x43 cm 
 
Dimension (with packing) WxHxD 
23x31x42,3 cm 
23x31x48,9 cm
Weight 
14,5 Kg 
15,5 Kg 
16,5 Kg 
18,5 Kg 
19,5 Kg
Equipped with 
 
 
2 output cables (IEC type)  
 
   
Input
Number of phases 
 
 
1Ph+N
Nominal voltage 
 
 
Single-phase 230Vac
Input voltage range  
 
 
+20%/-25%
Nominal frequency 
 
 
50/60 Hz (automatic selection)
Input frequency range 
 
 
+/-10% 
  
Output
Number of phases 
 
 
1Ph+N
Nominal voltage 
 
 
Single-phase 230Vac
Voltage regulation (Line mode) 
 
 
VR (Automatic Voltage Regulation)
Voltage regulation (Battery mode) 
 
 
+/-5% 
 
 
Frequency 
 
 
50/60 Hz (automatic selection)
Inverter waveform 
 
 
Sinewave 
 
Overload capability 
 
  110% for 60 s; 110-120% for 30 s; >120% for 20 ms   
Transfer time 
 
 
2 ms (typical)
Outlets 
3 UPS outputs (IEC 320 - C13 type) + 1 only fi ltered output (IEC 320 - C13 type) 
4 UPS outputs (IEC 320 - C13 type)
Battery
Type 
 
 
Lead acid, sealed, maintenance free 
 
Batteries number 
2 (internal) 
3 (internal)
Battery charge time (typical) 
 
 
4 hours 
Nominal battery voltage 
24Vdc 36Vdc
Battery specifi cation 
12Vdc - 7Ah 
12Vdc - 8Ah 
Backup time (typical) 
12 min 
10 min 
8 min 
6 min
Interfacing 
  
 
Interface (communication ports) 
RS232 e USB
Software 
UPSILON 2000, upgradeable free from 
www.tecnoware.com  (compatible with WINDOWS, UNIX, LINUX, ecc.)
Telephone/modem line protection 
RJ11     
Environmental specifi cation
Storage temperature  
From -15 to 40 °C (for UPS with battery inside, see “UPS (with batteries) storage” graphic) 
Working temperature 
From 0 to 40 °C (reccomended from 20 to 25 °C, for longer battery life see “UPS Battery life in operating conditions” graphic)
Humidity 
< 95% without condensation
Maximum altitude 
3000 m
IP protection 
IP20 
Certifi cations 
CE (Standards: Low Voltage Directive IEC EN 62040-1; EMC Directive IEC EN 62040-2; classifi cation IEC EN 62040-3)
Warranty 
  
Standard 
 24 months electronic parts and 24 months batteries
Extensions 
Optional
© 2012 Tecnoware Power Systems. The technical data may change without prior notice.