UPS Battery life in operating conditions
The higher is the temperature of the environment in which the
UPS works, the shorter is the battery life.
UPS works, the shorter is the battery life.
0
1
4
5
20
0
30
40
50
6
Battery life (years)
Temperature (C°)
25
35
45
3
2
1,5
40
60
80
100
0
6
9
12
5° C (41° F)
25° C (77° F)
30° C (88° F)
40° C (104° F)
25° C (77° F)
30° C (88° F)
40° C (104° F)
UPS (with batteries) storage
Battery capacity (%)
Storage (months)
It is necessary to
recharge the batteries
for a minimum
of 24 hours.
recharge the batteries
for a minimum
of 24 hours.
Attention: batteries
may not be recoverable
even when subjected
to charging.
may not be recoverable
even when subjected
to charging.
3
15
18
21
24
27
30
EASY INTERACTIVE
L
’A
Z
IE
N
D
A
UPS EXA
1.1-1.5-2.2-2.6-3.2
Specifi cation
UPS Model
EXA 1.1
EXA 1.5
EXA 2.2
EXA 2.6
EXA 3.2
Code
FGCEXA1K1 FGCEXA1K5 FGCEXA2K2
FGCEXA2K6 FGCEXA3K2
Nominal power
1100 VA
1500 VA
2200 VA
2600 VA
3200 VA
Active power
550 W
750 W
1100 W
1300 W
1600 W
Power factor
0.5
Technology
Line Interactive with stabilizer
Cooling
Natural
Audible noise
< 40 dBA at 1 m
Dimension (UPS) WxHxD
14,5x21,5x36 cm
14,5x21,5x43 cm
Dimension (with packing) WxHxD
23x31x42,3 cm
23x31x48,9 cm
Weight
14,5 Kg
15,5 Kg
16,5 Kg
18,5 Kg
19,5 Kg
Equipped with
2 output cables (IEC type)
Input
Number of phases
Number of phases
1Ph+N
Nominal voltage
Single-phase 230Vac
Input voltage range
+20%/-25%
Nominal frequency
50/60 Hz (automatic selection)
Input frequency range
+/-10%
Output
Number of phases
Number of phases
1Ph+N
Nominal voltage
Single-phase 230Vac
Voltage regulation (Line mode)
VR (Automatic Voltage Regulation)
Voltage regulation (Battery mode)
+/-5%
Frequency
50/60 Hz (automatic selection)
Inverter waveform
Sinewave
Overload capability
110% for 60 s; 110-120% for 30 s; >120% for 20 ms
Transfer time
2 ms (typical)
Outlets
3 UPS outputs (IEC 320 - C13 type) + 1 only fi ltered output (IEC 320 - C13 type)
4 UPS outputs (IEC 320 - C13 type)
Battery
Type
Type
Lead acid, sealed, maintenance free
Batteries number
2 (internal)
3 (internal)
Battery charge time (typical)
4 hours
Nominal battery voltage
24Vdc 36Vdc
Battery specifi cation
12Vdc - 7Ah
12Vdc - 8Ah
Backup time (typical)
12 min
10 min
8 min
6 min
Interfacing
Interface (communication ports)
RS232 e USB
Software
UPSILON 2000, upgradeable free from
www.tecnoware.com (compatible with WINDOWS, UNIX, LINUX, ecc.)
Telephone/modem line protection
RJ11
Environmental specifi cation
Storage temperature
From -15 to 40 °C (for UPS with battery inside, see “UPS (with batteries) storage” graphic)
Working temperature
From 0 to 40 °C (reccomended from 20 to 25 °C, for longer battery life see “UPS Battery life in operating conditions” graphic)
Humidity
< 95% without condensation
Maximum altitude
3000 m
IP protection
IP20
Certifi cations
CE (Standards: Low Voltage Directive IEC EN 62040-1; EMC Directive IEC EN 62040-2; classifi cation IEC EN 62040-3)
Warranty
Standard
24 months electronic parts and 24 months batteries
Extensions
Optional
© 2012 Tecnoware Power Systems. The technical data may change without prior notice.