Tripp Lite SmartOnline SU8000RT3UN50TF Manual De Usuario
Output voltage
regulation (line
mode)
regulation (line
mode)
+/- 2%
Output voltage
regulation (Economy
line mode)
regulation (Economy
line mode)
+/- 10%
Output voltage
regulation (Battery
mode)
regulation (Battery
mode)
+/- 2%
Built-in UPS output
receptacles
receptacles
12 5-15/20R outlet(s); 4 L6-20R outlet(s); 2 L6-30R outlet(s)
Output circuit
breaker
breaker
20A double-pole (x2) protects 2 L6-20R outlets each, 30A double-pole (x2) protects 1 L6-30R outlets each, 20A
single-pole (x4) protect 3 5-15/20R outlets each
single-pole (x4) protect 3 5-15/20R outlets each
Output AC waveform
(AC mode)
(AC mode)
Pure Sine wave
Output AC waveform
(battery mode)
(battery mode)
Pure Sine wave
INPUT
Rated input current
(at maximum load)
(at maximum load)
44.2A (208V)
Nominal Input
Voltage(s) Supported
Voltage(s) Supported
208V AC
UPS input
connection type
connection type
Hubbell CS8265; Hardwire
UPS input
connection
description
connection
description
3 wire single phase input (L1, L2, G)
UPS Input cord
length (ft.)
length (ft.)
10
UPS Input cord
length (m)
length (m)
3
Recommended
Electrical Service
Electrical Service
208V 50A
BATTERY
Full load runtime
(minutes)
(minutes)
5.5 min. (7200w)
Half load runtime
(minutes)
(minutes)
13.5 min. (3600w)
Expandable battery
runtime
runtime
Supports extended runtime with optional external battery packs
External battery
pack compatibility
pack compatibility
BP240V10RT3U
;
BP240V557C-1PH
;
BP240V787C-1PH
;
BP240V1037C-1PH
;
BP240V1407C-1PH
DC system voltage
(VDC)
(VDC)
240
Battery recharge
rate (included
batteries)
rate (included
batteries)
Less than 6 hours from 10% to 90%
Battery replacement
description
description
Hot-swappable, user replaceable external battery packs