Network  
 
 
 
Management Card 
User Manual 
 
 
 
Network Management Card
 – User Manual 
34003676EN/HA
 
Page 
8/81
 
 
NMC Transverse for UPS, in UPS slot, like the MGE Galaxy PW, MGE Galaxy PW 1000, MGE Galaxy 
3000, MGE Galaxy 4000 US, MGE Galaxy 5000, MGE Galaxy 5000 US 
 
NMC Transverse for UPS,
 
using the Network Management Link, like the Comet 3000, Comet S31, MGE 
Galaxy 6000, MGE Galaxy 9000, EPS 6000 US, EPS 7000 US, EPS 8000 US 
 
NMC Transverse for STS, in STS slot, like the MGE Epsilon STS and MGE Upsilon STS 
The Network Management Cards acquire information on the operation status of the UPS / STS systems and 
provide remote control of these systems by means of an ETHERNET network from any SNMP administration 
station or Web browser. They also supply alarms to the Network Shutdown Modules to trigger shutdown or 
other automatic actions for protected servers. 
 
A simple html browser is used for supervision and configuration. 
Network Management Cards are compatible with : 
  
 
Network Shutdown Modules 
 
Entreprise Power Manager 
 
Management-Pac 2 ? 
 
ISXC 
1.3  Presentation of the Environment Sensor solution 
The 
Environment Sensor
 solution comprises a box to be connected to the Card Settings port of the 
Network Management Cards: 
Environment Sensor enables measurement of temperature and humidity around the UPS, consideration of 
external alarms via 2 dry contacts and notification of alarms according to pre-programmed thresholds. 
1.4  Direct sending of E-mail 
When a UPS / STS event occurs, the Network Management Card can directly notify up to 4 intranet or 
extranet addressees by e-mail (see 
Email Notification
 and 
Email Message Settings
). 
1.5  Sending text messages (SMS) 
SMS messages can be sent by specific configuration of the e-mail function via the internet access 
providers making the e-mail / SMS transfer. 
1.6  Compatibility with the Network Management Systems (NMS) – Trap sending 
The Network Management Cards are compatible with the major Network Management Systems (IBM Tivoli, 
CA Unicenter, HP Insight Manager ..),. The Management-Pac 2 offering includes the necessary SNMP 
plug-in to allow an easy integration in the NMS. Events are notified by SNMP trap 
 
NMS can subscribe on page “
Notified Application
” 
 
SNMP sequences are described in chapter “Server protection” 
The trap list can be looked over in the document “Agent's MIB description” available on 
apc.com