1.7  Technical data 
1.7.1  Configuration 
The user can configure the card with one of the following means:  
 
Web browser 
 
Local serial link 
 
Telnet console 
 
BOOTP/DHCP 
 
Mupgrade 
1.7.2  Administration 
 
Up to 50 workstations protected  
 
Up to 15 browsers connected at the same time  
 
E-mail sending configurable according to UPS alarms and transmission of a periodical report  
 
Measurement of temperature and humidity, adjustable thresholds, possibility of sending e-mails and shutting 
down the installation  
 
Control of UPS on/off switching via the HTML  interface  
 
Adjustment and control Power via the HTML interface, sequential starting of the installation  and 
optimisation of backup time by shutting down non-priority systems  
 
Adjustment of date and time via NTP server  - Daylight Saving Time management 
 
Protection by encrypted password.  
 
Protection by secured connection SSL and SSH 
 
Saving of logs in the non-volatile memory 
 
Automatic language detection according to browser configuration.  
 
Languages available: English / French / Spanish / German / Italian 
 
On-line help available for each page 
 
Card firmware updated via the network  
 
Card configuration deployment on your installed base through network utility (Mupgrade) 
1.7.3  Network 
 
Fast ETHERNET 10/100 Mbits compatibility with auto-negotiation on the RJ45 outlet 
 
SNMP trap port modifiable (by default = 162) 
1.7.4  MIB (Management Information Base) 
 
MIB IETF UPS (RFC1628) for UPS 
 
MIB MGE V1.7 AD, for UPS 
 
MIB MGE V2.2 AA, for STS 
 
1.7.5  Environment sensor 
 
Temperature measurement from 0 to 70 °C with +/- 1° C accuracy  
 
Measurement of humidity from 0 to 100 % with +/- 6 % accuracy 
 
Min / max time-stamped function for temperature and humidity 
 
Choice of temperature readings in Celsius or Fahrenheit 
 
High and low thresholds, hysteresis and offset adjustable via Web interface