Tripp Lite 2200 VA UPS SMART2200RMXL2UP Manual De Usuario

Los códigos de productos
SMART2200RMXL2UP
Descargar
Página de 6
Includes NEMA 5-20P input plug, 4 NEMA 5-15R and 4 5-15/20R output receptacles
Two individually switched outlets support automatic load shedding and real time remote-reboot operations of 2 individual connected devices
Network management interfaces support simultaneous communications via USB, DB9 serial and optional SNMP/Web management
accessory card slot
Optional SNMPWEBCARD offers remote management and direct UPS control via built-in network interface
Optional ENVIROSENSE accessory reports temperature and humidity (requires SNMPWEBCARD) 
ENVIROSENSE also supports the connection of up to 4 SRSWITCH door access sensors and user supplied contact closure monitoring
accessories 
HID-compliant USB interface enables full integration with built-in power management and auto shutdown features of Windows and Mac OS
X
Supports detailed monitoring of equipment load levels, self-test data and utility power conditions via all 3 network interfaces at once
Includes PowerAlert monitoring software with USB and serial cables
Emergency Power Off (EPO) interface
3-stage metered current monitoring and battery charge status LEDs
Utility power and voltage regulation LEDs, audible alarm and self self-test ability
Supports 2U rackmount installation with a maximum depth of 19 inches
4-post rackmount accessories included; 2-9USTAND tower stands and 2POSTRMKITWM 2 post rackmount or wallmount installation kit
available
Field-replaceable, hot-swappable internal batteries and external battery packs
Specifications
OUTPUT
Output Volt Amp
Capacity (VA)
2200
Output kVA capacity
(kVA)
2.2
Output Watt Capacity
(watts)
1920
Output kW capacity
1.92
Output power factor
0.87
Output Capacity Details
Supports 1750 watts when set to 110V nominal; Supports 1600 watts when set to 100V nominal
Nominal Output
Voltage(s) Supported
100V; 110V; 120V
Nominal Voltage details
120V factory setting
Frequency compatibility
50 / 60 Hz
Output voltage regulation
(line mode)
120V (+6% / -14%); 110V (+6% / -12%); 100V (+11% / -7%)
Output voltage regulation
(Battery mode)
+/- 5%
Built-in UPS output
receptacles
4 5-15R outlet(s); 4 5-15/20R outlet(s)
Built-in controllable
switched load banks
Two switchable single-outlet 5-15R load banks
Output AC waveform (AC
mode)
Sine wave
Output AC waveform
(battery mode)
Pure Sine wave
INPUT