Connect the test cable to the BENNING IT 110/ BENNING IT 120 B.
Step 2  
Set the following limit value:
 
 
 High limit resistance value
Step 3 
 Before performing the lowΩ measurement, compensate test lead resistance as follows:
1.   Short test lead first as shown in figure 5.5.
Fig. 5.5: Shorted test leads
2.   Press the TEST key in order to perform regular measurement. Result close to 0.00 Ω is
displayed.
3.   Press the CAL key. After performing test lead compensation, the compensated test lead indica-
tor (Co) is displayed.
4.   In order to annul potential compensation follow the procedure described in this step with open 
test leads. After annulling compensation, the compensation indicator disappears.
Compensation performed in this function is also considered in the Continuity measurement.
Step 4 
 Connect test cable to the item under test. Follow the connection diagram shown in fi-
gures 5.6 and 5.7 to perform 
LowΩ resistance measurement. Use the Help function if 
necessary..
Fig. 5.6: Connection of universal test cable and optional probe test lead (extension)