Benning IT 120 B 044102 Manual De Usuario

Los códigos de productos
044102
Descargar
Página de 80
58
The number of possible tests
with a new set of batteries 
 
 
bis zu 5500
Automatic polarity reversal of the test voltage
9.2.2  Continuity
Measuring range (mA)
Resolution (mA)
Accuracy
0.0 - 99.9
0.1
± (5 % of reading + 3 digits)
100 - 1999
1
Open-circuit voltage 
 
 
 
6.5 V
DC
 - 9 V
DC
Short-circuit current 
 
 
 
max. 8.5 mA
Test lead compensation
up to 5 Ω
9.3  RCD
9.3.1  General data
Nominal residual current 
 
 
10 mA, 30 mA, 100 mA, 300 mA, 500 mA, 1000 mA
Accuracy of 
nominal residual current measurement   
-0 / +0.1
⋅I
; I
 = I
∆N
, 2
×I
∆N
, 5
×I
∆N
 
 
 
 
 
 
 
 
-0.1
⋅I
 / +0; I
 = ½
×I
∆N
Test current shape 
 
 
 
 Sine-wave (AC type), pulsed (A type), smooth 
 direct current (B type)
RCD type: 
 
 
 
 
 general (G, non-delayed), selective (S, time-delayed)
Test current starting polarity 
 
 
0° or 180°
Voltage range   
 
 
 
100 V - 264 V (45 Hz - 65 Hz)
RCD test current selection (r.m.s. value calculated to 20 ms) according to IEC 61009:
I
N
 
× ½
I
N
 
× 1
I
N
 
× 2
I
N
 
× 5
RCD I
I
N
 (mA)
AC
A
B
AC
A
B
AC
A
B
AC
A
B
AC
A
B
10
5
3.5
5
10
20
20
20
40
40
50
100
100
30
15
10.5
15
30
42
60
60
84
120
150
212
300
100
50
35
50
100
141
200
200
282
400
500
707
1000
300
150
105
150
300
424
600
600
848
*)
1500
*)
*)
500
250
175
250
500
707
1000 1000 1410
*)
2500
*)
*)
1000
500
350
500
1000 1410
*)
2000
*)
*)
*)
*)
*)
*)
*)   
 
not available 
Type AC: 
sinusoidal testing current
Type A:  
pulsating testing current
Type B:  
testing current is a smooth direct current
9.3.2  Contact voltage
Measuring range according to EN61557-6: 3.0 up to 99.9 V at 50 V
Measuring range according to EN61557-6: 3.0 up to 49 V at 25 V
Measuring range (mA)
Resolution (mA)
Accuracy
0.0 (3.0) - 9.9
0.1
(-0 % / +10 %) of reading +2 digits
10.0 - 99.9
0.1
(-0 % / +10 %) of reading