TESTBOY TV 450 
Testing RCD 
 
38 
RCD type 
Contact voltage Uc 
proportional to 
Rated I
ΔN
 
 
AC G 
1.05
×I
ΔN
 
AC 
S
 
2
×1.05×I
ΔN
 
any 
A G 
1.4
×1.05×I
ΔN
 
S
 
2
×1.4×1.05×I
ΔN
 
≥ 30 mA 
A G 
2
×1.05×I
ΔN
 
S
 
2
×2×1.05×I
ΔN
 
< 30 mA 
Both models 
B G 
2
×1.05×I
ΔN
 
S
 
2
×2×1.05×I
ΔN
 
any Model 
TESTBOY 
TV 450 (Type B) 
only 
Table 5.1: Relationship between Uc and I
Δ
Loop resistance is indicative and calculated from Uc result (without additional 
proportional factors) according to:
N
C
L
I
U
R
Δ
=
 
 
 
 
UK version 
Figure 5.18: Example of contact voltage measurement results 
Displayed results: 
Uc........Contact voltage. 
Rl.........Fault loop resistance. 
 
5.4.2 Trip-out time (RCDt) 
 
Trip-out time measurement verifies the sensitivity of the RCD at different residual 
currents.  
 
Trip-out time measurement procedure 
 
* model TESTBOY TV 450 (TYPE B) 
‰
 
Select the 
RCD
 function using the function selector switch. 
‰
 
Set sub-function RCDt. 
‰
 
Set test parameters (if necessary). 
‰
 
Connect test cable to the instrument. 
‰
 
Connect test leads to the item to be tested (see 
figure 5.17). 
‰
 
Press the TEST key to perform the measurement. 
‰
 
Store the result by pressing the MEM key (optional)*.