Testboy TV 455VDE-tester Testboy TV 455 用户手册
产品代码
Testboy TV 455
TESTBOY TV 450
Testing RCD
38
RCD type
Contact voltage Uc
proportional to
Rated I
ΔN
AC G
1.05
×I
ΔN
AC
S
2
×1.05×I
ΔN
any
A G
1.4
×1.05×I
ΔN
A
S
2
×1.4×1.05×I
ΔN
≥ 30 mA
A G
2
×1.05×I
ΔN
A
S
2
×2×1.05×I
ΔN
< 30 mA
Both models
B G
2
×1.05×I
ΔN
B
S
2
×2×1.05×I
ΔN
any Model
TESTBOY
TV 450 (Type B)
only
Table 5.1: Relationship between Uc and I
ΔN
Loop resistance is indicative and calculated from Uc result (without additional
proportional factors) according to:
N
C
L
I
U
R
Δ
=
.
UK version
Figure 5.18: Example of contact voltage measurement results
Displayed results:
Uc........Contact voltage.
Rl.........Fault loop resistance.
Uc........Contact voltage.
Rl.........Fault loop resistance.
5.4.2 Trip-out time (RCDt)
Trip-out time measurement verifies the sensitivity of the RCD at different residual
currents.
Trip-out time measurement procedure
* model TESTBOY TV 450 (TYPE B)
Select the
RCD
function using the function selector switch.
Set sub-function RCDt.
Set test parameters (if necessary).
Connect test cable to the instrument.
Connect test leads to the item to be tested (see
figure 5.17).
Press the TEST key to perform the measurement.
Store the result by pressing the MEM key (optional)*.