Testboy TV 455VDE-tester Testboy TV 455 Manual De Usuario
Los códigos de productos
Testboy TV 455
TESTBOY TV 450
Line impedance
45
5.6 Line impedance and prospective short-circuit current
Line impedance is measured in loop comprising of mains voltage source and line wiring.
It is covered by requirements of the EN 61557-3 standard.
See chapter
4.1 Function selection for instructions on
key functionality.
Figure 5.26: Line impedance
Test parameters for line impedance measurement
FUSE type
Selection of fuse type [---, NV, gG, B, C, K, D]
FUSE I
Rated current of selected fuse
FUSE T
Maximum breaking time of selected fuse
Lim
Minimum short circuit current for selected fuse.
See Appendix A for reference fuse data.
Connections for measurement of line impedance
Connections for measurement of line impedance
L1
L2
L3
N
L2
L3
N
PE
R
E
Ro
L
PE
N
L/L
1
N/L2
PE/L3
N/
L
2
L
/L
1
PE
/L
3
Figure 5.27: Phase-neutral or phase-phase line impedance measurement – connection
of plug commander and 3-wire test lead
Line impedance measurement procedure
* model TESTBOY TV 450 (TYPE B)
Select the
Z-LINE
function using the function selector switch.
Select test parameters (optional).
Connect test cable to the instrument.
Connect test leads to the to the item to be tested (see
figure 5.27).
Press the TEST key to perform the measurement.
Store the result by pressing the MEM key (optional)*.