Testboy TV 455VDE-tester Testboy TV 455 Manuale Utente

Codici prodotto
Testboy TV 455
Pagina di 76
TESTBOY TV 450 
Line impedance 
 
45 
5.6  Line impedance and prospective short-circuit current 
 
Line impedance is measured in loop comprising of mains voltage source and line wiring. 
It is covered by requirements of the EN 61557-3 standard. 
 
 
See chapter 
4.1 Function selection for instructions on 
key functionality. 
Figure 5.26: Line impedance 
 
Test parameters for line impedance measurement
 
 
FUSE type 
Selection of fuse type [---, NV, gG, B, C, K, D] 
FUSE I 
Rated current of selected fuse 
FUSE T 
Maximum breaking time of selected fuse 
Lim 
Minimum short circuit current for selected fuse. 
See Appendix A for reference fuse data. 
 
Connections for measurement of line impedance 
 
L1
L2
L3
N
PE
R
E
Ro
L
PE
N
L/L
1
N/L2
PE/L3
N/
L
2
L
/L
1
PE
/L
3
 
Figure 5.27: Phase-neutral or phase-phase line impedance measurement – connection 
of plug commander and 3-wire test lead 
Line impedance measurement procedure 
 
* model TESTBOY TV 450 (TYPE B) 
‰
 
Select the 
Z-LINE
 function using the function selector switch. 
‰
 
Select test parameters (optional). 
‰
 
Connect test cable to the instrument. 
‰
 
Connect test leads to the to the item to be tested (see 
figure 5.27). 
‰
 
Press the TEST key to perform the measurement. 
‰
 
Store the result by pressing the MEM key (optional)*.