2-5
CH 2/ Voltage Measurement Cables and Current Probe Connections
Measurement 
cable set with 
optional fuse 
diagram
WARNING
To avoid the risk of electric shock or burns, always connect the safety (or earth) 
ground before making any other connections.
WARNING
To reduce the risk of fire, electrical shock, or physical injury it is strongly 
recommended to fuse the voltage measurement inputs.
Fuses must be located as close to the load as possible to maximize protection.
WARNING
For continued protection against risk of fire or shock hazard replace only with 
same type and rating of recommended fuse.
Use only fast blow type fuse which is rated 600V. Recommended fuse type is 
Littelfuse, part number KLKD0.30 rated 600V AC/DC, 0.3A fast blow.
WARNING
Do not replace fuse again if failure is repeated. Repeated failure indicates a 
defective condition that will not clear with replacement of the fuse. Refer 
condition to a qualified technician.
Contact Dranetz-BMI Customer Service for more information on the fused voltage 
adapter. Refer to Dranetz-BMI Information Sheet titled Model FVA - Fuse Voltage 
Adapter, P/N 899107.
EP-11.vsd