ConiuGo 700100107 EasyGuard II 700100107 Manual De Usuario
Los códigos de productos
700100107
14
Revision 9.0
GSM Alarm & Telemetry systems
•
0h 0m 0s / 1.1.2000
Reports the current time and date. Not correct setted ex works.
•
123456789 ABC
This is the numbering of the digital entrances. This is indicated in HEX
code. Please note: A = input 10, B = input 11 and C = input 12.
•
DIGITAL INPUTS
Here is reported the condition of the digital inputs. If unused or in rest they
are on level “1”. If by a sensor the input is pulled to ground the level jumps
to a “0”. These conditions also have to be taken into account for the set-
tings in the connection settings.
Example:
If you need to trigger a reaction after an event occurring on a digital input,
you have to enter a “0” for this digital inputs in the connections settings.
Please take into account that closing the switch or relay contact con-
nected to a digital input will set this input to “0”!
•
DIGITAL OUTPUTS
By the “connection settings” the digital outputs become corresponding to an
“event” or a combination of several “events”. If this happens the level of the
digital output jumps from “0” to “1” and switches the corresponding relay
output.
•
TIME FRAMES
If a time frame is defined and is used in the connection settings, a “1” ap-
pears in the connection settings as long as this time period is active. A
maximum of 3 time frames is possible to be defined.
•
INCOMING SMS
If a SMS is coming in and is recognised by the module, the level indicating
this SMS indication changes from “0” to “1”.
•
ANALOG INPUTS
In the settings for the analog inputs you are able to set a minimum and a
maximum value to define a range in which the input signal indicates an
event. That means that the GSM module supervises the input and has a