International English                                                                                        3. COMMISSIONING
32
MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
Changing parameters with the BOP
The following description shows how to change the parameter P1082, use this
description as a guide for setting any parameters using the ‘BOP’.
Step
Result on display
1 Press 
 to access parameters
Hz
P(1)
r
0000
2 Press 
  until P0010 is displayed
Hz
P(1)
P0010
3
Press 
 to access P0010 parameter
value level
Hz
P(1)
0
4 Press 
 to set P0010 = 1
Hz
P(1)
1
5 Press 
  to save and exit parameter
value level
Hz
P(1)
P0010
6 Press 
 until P1082 is displayed
Hz
P(1)
P1082
7 Press 
 to access P1082 parameter
value level
Hz
P(1)
50.00
8
Press 
 to select desired maximum
frequency
Hz
P(1)
35.00
9 Press 
 to save and exit parameter
value level
Hz
P(1)
P1082
10 Press 
 to return to P0010
Hz
P(1)
P0010
11
Press 
 to access P0010 parameter
value level
Hz
P(1)
1
12 Press 
 to return value to P0010 = 0
Hz
P(1)
0
13 Press 
 to save and exit parameter
value level
Hz
P(1)
P0010
14 Press 
  to return to r0000
Hz
P(1)
r
0000
15 Press 
 to exit Parameterization
Hz
P(1)
35.00
The LCD will alternate between actual
frequency and the requested frequency
setpoint
Hz
P(1)
00.00
Figure 3-4
Changing parameters via the BOP
The required maximum frequency has now been stored.
Note - Busy Message
In some cases - when changing parameter values - the display on the BOP shows
" - - - -". This means the inverter is busy with tasks of higher priority.