3. COMMISSIONING                                                                                          International English
MICROMASTER 420 Operating Instructions
33
6SE6400-5AA00-0BP0
Motor data for parameterization
Figure 3-5   Typical Motor Rating Plate Example
Note
♦  Changing motor parameters is not possible unless P0010=3.
♦  Ensure that the inverter is configured correctly to the motor, i.e. in the above example
delta terminal connection is for 230 V.
External motor thermal overload protection
When operated below rated speed, the
cooling effect of fans fitted to the motor
shaft is reduced. Consequentially, most
motors require de-rating for continuous
operation at low frequencies. To ensure
that the motors are protected against
overheating under these conditions, a
PTC temperature sensor must be fitted to
the motor and connected to the inverter
control terminals as shown in Figure 3-6.
Figure 3-6
Motor Overload PTC Connection
Note:
To enable the trip function, set parameter P0701, P0702 or P0703 = 29.
Inverter Control
Terminals
8
9
5, 6
or 7
1 k
Ω
Motor
PTC
50 Hz
230-400V
0.61 0.35 A
Cos j0.81
Cos j0.81
95.75%
0.12kW
2800 / min
3_Mot
IEC 56
IM B3
Nr. ED510 3053
IP54
Rot KL 16
60 Hz
440V Y
0.34A
0.14 kW
3310 /min
S.F. -- 1.15
12.022
I.CI.F
P0308 P0310
P0304
P0309
P0305 P0311
P0307