International English                                                                                 6. TROUBLESHOOTING
94
MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
6.3 
MICROMASTER 420 fault codes
In the event of a failure, the inverter switches off and a fault code appears on the display.
Table 6-2
MICROMASTER 420 Fault Codes
Fault Code
Description
Possible Causes
Diagnosis & Remedy
F0001
Overcurrent
1. Motor power does not
    correspond to the inverter
    power.
2. Motor lead short circuit
3. Earth fault
1. Check whether the motor power
    corresponds to the inverter
    power.
2. Check that the cable length limits
    have not been exceeded.
3. Check motor cable and motor for
    short-circuits and earth faults.
4. Check whether the motor
    parameters correspond with the
    motor being used.
5. Check the stator resistance
    (P0350).
6. Increase the ramp-up-time
    (P1120).
7. Reduce the boost set in (P1310),
    (P1311) and (P1312).
8. Check whether the motor is
    obstructed or overloaded.
F0002
Overvoltage
Supply voltage out of tolerance
load is regenerating.
1. Check whether the supply voltage
    is within the limits indicated on the
    rating plate.
2. Check if dc-link voltage
    controller (P1240)
 
is enabled and
    parameterized correctly.
3. Increase the ramp-down time
    (P1121).
F0003
Undervoltage
Mains supply removed when
inverter is running.
1. Check whether the supply voltage
    is within the limits indicated on the
    rating plate.
2. Check the supply is not subject to
    temporary failures or voltage
    reductions.
F0004
Inverter
Overtemperature
Ambient temperature outside of
limits,
Fan failure
1. Check that the integral fan rotates
    when drive is running.
2. Check if pulse frequency is set to
    default value.
3. Ambient temperature could be
    higher than specified for the
    inverter.
4. Check that air inlet and outlet
    points are not obstructed.
F0005
Inverter I
2
T
Inverter is overloaded
1. Check if load duty-cycle is within
    specified limits.
2. Check that motor power
    corresponds to inverter power
F0011
Motor Overtemperature
I
2
T
1. Motor overloaded.
2. Motor data incorrect.
3. Check parameter for motor
    thermal time constant.
4. Check parameter for motor I
2
t
    warning level.
5. Long time period operating at
    low speeds
1. Check motor data.
2. Check loading on motor.
3. Boost settings too high (P1310,
    P1311, P1312)
F0041
Stator resistance
measurement failure
Stator resistance measurement
failure
1. Check if the motor is connected to
    the inverter
2. Check that the motor data has
    been entered correctly.